Room Size Restriction
The appliances are connected via an air duct system to one or more rooms. The bottom of the air inlet of the air duct should be at a height > 7.3ft/2.2m
from the floor. In UL/CSA 60335-2-40 the refrigerant belongs to mildly flammable refrigerants which will limit the room area of the system service.
Similarly, the total amount of refrigerant in the system should be less than or equal to the maximum allowable refrigerant charge, which depends on
the room area services by the system.
Table 3 — Airflow Information
Table 4 — Compatible Models
MODEL 09K 12K 18K 24K 36K 48K 60K
NOMINAL AIR
VOLUME CFM (M
3
/H)
324 (550) 382 (650) 647 (1100) 824 (1400) 1176 (2000) 1588 (2700) 2000 (3400)
CAPACITY INDOOR OUTDOOR
06K
45MBDAQ06XA3 37MAHAQ06AA3
09K/12K
45MBDAQ12XA3
45MBDAQ12XH3
37MAHAQ09AA3
37MAHAQ12AA3
37MARAQ09AA3
37MARAQ12AA3
18K
45MBDAQ18XA3
45MBDAQ18XH3
37MAHAQ18AA3
37MARAQ18AA3
24K 45MBDAQ24XH3
37MAHAQ24AA3
37MARAQ24AA3
36K 45MBDAQ36XH3
37MBHAQ36AA3
37MBRAQ36AA3
48K 45MBDAQ48XH3
37MBHAQ48AA3
37MBRAQ48AA3
58K 45MBDAQ58XH3
37MBHAQ58AA3
37MBRAQ58AA3