DIP SWITCH SETTINGS
Table 28 — Dip Switch Settings
NO. DIAL CODE FUNCTION ON OFF 1 ON&2 ON 1 ON&2 OFF 1 OFF&2 ON 1 OFF&2 OFF
1SW1-1
COOLING and HEATING or
COOLING Only setting
COOLING Only
[Default]
COOLING
and HEATING
N/A N/A N/A N/A
2 SW2-1&SW2-2
Indoor fan stop temperature
(TEL0) for normal anti-cold
air function in HEATING
mode
N/A N/A
According to
EEROM
setting
15°C 8°C [Default]24°C
3 SW2-3&SW2-4
Heating temperature
compensation
N/A N/A
According to
EEROM
setting
4°C 2°C [Default]6°C
4
SW8-1&SW8-2+
Rotary Switch S1
Central control address
selection
N/A N/A 48+S1 16+S1 32+S1 S1
5 SW8-3 Auto-restart setting
Will not
maintain previous
setting
[Default]
Run at
previous setting
N/A N/A N/A N/A
6 Rotary Switch ENC1 Capacity selection
[Default]
Auto detection: ENC1=0; 6K: ENC1=1; 9K:ENC1=2; 12K: ENC1=3; 18K:ENC1=5; 24K: ENC1=8; 36K:
ENC1=A; 48K: ENC1=C; 60K: ENC1=E