125
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — PRESSURES
MODE — SET POINTS
MODE — INPUTS
*The display text changes depending on the remote switch configuration (Configuration
→
UNIT
→
RM.CF). If RM.CF is set to 0 (No Remote
Switch), then the display text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or
“Unoccupied.” If RM.CF is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If RM.CF is set to 3 (Override Switch), then the display
text will be “No Override” or “Override.”
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
AIR.P AIR PRESSURES
→
SP Static Pressure "H2O SP
→
BP Building Pressure "H2O BP
REF.P REFRIGERANT PRESSURES
→
DP.A Cir A Discharge Pressure PSIG DP_A
→
SP.A Cir A Suction Pressure PSIG SP_A
→
DP.B Cir B Discharge Pressure PSIG DP_B
→
SP.B Cir B Suction Pressure PSIG SP_B
ITEM DESCRIPTION RANGE UNITS CCN POINT DEFAULT
OHSP Occupied Heat Setpoint 40-99 dF OHSP 68
OCSP Occupied Cool Setpoint 40-99 dF OCSP 75
UHSP Unoccupied Heat Setpoint 40-99 dF UHSP 55
UCSP Unoccupied Cool Setpoint 40-99 dF UCSP 90
GAP Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5
V.C . ON VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5
V.C . OF VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2
SASP Supply Air Setpoint 45-75 dF SASP 55
SA.HI Supply Air Setpoint Hi 45-75 dF SASP_HI 55
SA.LO Supply Air Setpoint Lo 45-75 dF SASP_LO 60
SA.HT Heating Supply Air Setpt 80-120 dF SASPHEAT 85
T.PRG Tempering Purge SASP –20-80 dF TEMPPURG 50
T.CL Tempering in Cool SASP 5-75 dF TEMPCOOL 5
T.V.OC Tempering Vent Occ SASP –20-80 dF TEMPVOCC 65
T.V.UN Tempering Vent Unocc. SASP –20-80 dF TEMPVUNC 50
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
GEN.I GENERAL INPUTS
→
FLT.S Filter Status Input DRTY/CLN FLTS forcible
→
G.FAN Fan Request From IGC ON/OFF IGCFAN
→
REMT Remote Input State * RMTIN forcible
→
E.SW Economizer Control Input YES/NO ECOSW forcible
→
E.ENA Remote Economizer Enable YES/NO ECONENBL forcible
→
E.OVR Econo Position Override YES/NO ECOORIDE forcible
→
S.FN.S Supply Fan Status Switch ON/OFF SFS forcible
→
DL.S1 Demand Limit Switch 1 ON/OFF DMD_SW1 forcible
→
DL.S2 Demand Limit Switch 2 ON/OFF DMD_SW2 forcible
→
DH.IN Dehumidify Switch Input ON/OFF DHDISCIN forcible
FD.BK COMPRESSOR FEEDBACK
→
CS.A1 Compressor A1 Feedback ON/OFF CSB_A1
→
CS.A2 Compressor A2 Feedback ON/OFF CSB_A2
→
CS.B1 Compressor B1 Feedback ON/OFF CSB_B1
→
CS.B2 Compressor B2 Feedback ON/OFF CSB_B2
STAT THERMOSTAT INPUTS
→
G Thermostat G Input ON/OFF G forcible
→
W1 Thermostat W1 Input ON/OFF W1 forcible
→
W2 Thermostat W2 Input ON/OFF W2 forcible
→
Y1 Thermostat Y1 Input ON/OFF Y1 forcible
→
Y2 Thermostat Y2 Input ON/OFF Y2 forcible
FIRE FIRE-SMOKE INPUTS
→
FSD Fire Shutdown Input ALARM/NORMAL FSD forcible
→
PRES Pressurization Input ALARM/NORMAL PRES forcible
→
EVAC Evacuation Input ALARM/NORMAL EVAC forcible
→
PURG Smoke Purge Input ALARM/NORMAL PURG forcible
REL.H RELATIVE HUMIDITY
→
OA.RH Outside Air Rel. Humidity % OARH forcible
→
OA.EN Outdoor Air Enthalpy OAE
→
OA.DP OutsideAir Dewpoint Temp dF OADEWTMP
→
RA.RH Return Air Rel. Humidity % RARH forcible
→
RA.EN Return Air Enthalpy RAE
AIR.Q AIR QUALITY SENSORS
→
IAQ.I IAQ - Discrete Input HIGH/LOW IAQIN forcible
→
IAQ IAQ - PPM Return CO2 IAQ forcible
→
OAQ OAQ - PPM Return CO2 OAQ forcible
→
DAQ Diff.Air Quality in PPM DAQ
→
IQ.P.O IAQ Min.Pos. Override % IAQMINOV forcible
RSET RESET INPUTS
→
SA.S.R Supply Air Setpnt. Reset ^F SASPRSET forcible
→
SP.RS Static Pressure Reset SPRESET forcible