APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — INPUTS (cont)
*The display text changes depending on the remote switch configuration (Configuration
→
UNIT
→
RM.CF). If RM.CF is set to 0 (No Remote
Switch), then the display text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or
“Unoccupied.” If RM.CF is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If RM.CF is set to 3 (Override Switch), then the display
text will be “No Override” or “Override.”
MODE — OUTPUTS
MODE — CONFIGURATION
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
4-20 4-20 MILLIAMP INPUTS
→
IAQ.M IAQ Milliamps ma IAQ_MA
→
OAQ.M OAQ Milliamps ma OAQ_MA
→
SP.R.M SP Reset milliamps ma SPRST_MA
→
DML.M 4-20 ma Demand Signal ma DMDLMTMA forcible
→
EDR.M EDT Reset Milliamps ma EDTRESMA
→
ORH.M OARH Milliamps ma OARH_MA
→
RRH.M RARH Milliamps ma RARH_MA
→
BP.M BP Milliamps ma BP_MA
→
BP.M.T Bldg. Pressure Trim (ma) –2.0 - 2.0 BPMATRIM config
→
SP.M SP Milliamps ma SP_MA
→
SP.M.T Static Press. Trim (ma) –2.0 - 2.0 SPMATRIM config
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
FANS FANS
→
S.FAN Supply Fan Relay ON/OFF SFAN_RLY
→
S.VFD Supply Fan VFD Speed 0-100 % SFAN_VFD
→
P.E .A Power Exhaust Relay A ON/OFF PE_A
→
P.E .B Power Exhaust Relay B ON/OFF PE_B
→
P.E .C Power Exhaust Relay C ON/OFF PE_C
→
CD.F.A Condenser Fan Circuit A ON/OFF CONDFANA
→
CD.F.B Condenser Fan Circuit B ON/OFF CONDFANB
COOL COOLING
→
A1 Compressor A1 Relay ON/OFF CMPA1
→
A2 Compressor A2 Relay ON/OFF CMPA2
→
MLV Min. Load Valve (HGBP) ON/OFF MLV
→
B1 Compressor B1 Relay ON/OFF CMPB1
→
B2 Compressor B2 Relay ON/OFF CMPB2
HEAT HEATING
→
HT.1 Heat Relay 1 ON/OFF HS1
→
HT.2 Heat Relay 2 ON/OFF HS2
→
HT.3 Relay 3 W1 Gas Valve 2 ON/OFF HS3
→
HT.4 Relay 4 W2 Gas Valve 2 ON/OFF HS4
→
HT.5 Relay 5 W1 Gas Valve 3 ON/OFF HS5
→
HT.6 Relay 6 W2 Gas Valve 3 ON/OFF HS6
→
H.I.R Heat Interlock Relay ON/OFF HIR forcible
ECON ECONOMIZER
→
ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS
→
ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible
→
E.PWR Economizer Power Relay ON/OFF ECON_PWR forcible
GEN.O GENERAL OUTPUTS
ALRM Remote Alarm/Aux Relay ON/OFF ALRM forcible
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
UNIT UNIT CONFIGURATION
→
C.TYP Machine Control Type 1 - 6 (multi-text strings) CTRLTYPE 4 35
→
CV.FN Fan Mode (0=Auto, 1=Cont) 0 - 1 (multi-text strings) FAN_MODE 1 35
→
RM.CF Remote Switch Config 0 - 3 (multi-text strings) RMTINCFG 0 35
→
CEM CEM Module Installed Yes/No CEM_BRD No 35
→
TCS.C Temp.Cmp.Strt.Cool Factr 0 - 60 min TCSTCOOL 0 35
→
TCS.H Temp.Cmp.Strt.Heat Factr 0 - 60 min TCSTHEAT 0 35
→
SFS.S Fan Fail Shuts Down Unit Yes/No SFS_SHUT No 35
→
SFS.M Fan Stat Monitoring Type 0 - 2 (multi-text strings) SFS_MON 0 35
→
VAV.S VAV Unocc.Fan Retry Time 0 - 720 min SAMPMINS 50 35
→
SIZE Unit Size (20-60) 20 - 60 UNITSIZE 20 35
→
DP.XR Disch.Press. Transducers Yes/No DP_TRANS No 36
→
SP.XR Suct. Pres. Trans. Type 0 - 1 (multi-text strings) SPXRTYPE 0 36
→
MAT.S MAT Calc Config 0 - 2 (multi-text strings) MAT_SEL 1 36
→
MAT.R Reset MAT Table Entries? Yes/No MATRESET No 36
→
ALTI Altitude……..in feet: 0 - 60000 ALTITUDE 0 36
→
DLAY Startup Delay Time 0 - 900 sec DELAY 0 36
→
STAT TSTAT-Both Heat and Cool Yes/No TSTATALL No 36
→
SENS INPUT SENSOR CONFIG 36
→
SENS
→
SPT.S Space Temp Sensor Enable/Disable SPTSENS Disable 36
→
SENS
→
SP.O.S Space Temp Offset Sensor Enable/Disable SPTOSENS Disable 36
→
SENS
→
SP.O.R Space Temp Offset Range 1 - 10 SPTO_RNG 5 36
→
SENS
→
RRH.S Return Air RH Sensor Enable/Disable RARHSENS Disable 36
→
SENS
→
FLT.S Filter Stat.Sw.Enabled ? Enable/Disable FLTS_ENA Disable 36