Fig. 7—48GP042-060 Unit Dimensions
C99074
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. [MM]
"A"
CENTER OF GRAVITY
IN. [MM]
lb. kg. X Y Z
48GP042060/090
208/230-1-60
208/230-3-60
460-3-60
382 173.3 38.98 [990.2] 23.0 [584.2] 16.3 [412.8] 16.6 [421.6]
48GP048090/115/130
208/230-1-60
208/230-3-60
460-3-60
421 191.0 38.98 [990.2] 21.5 [546.1] 16.6 [422.1] 18.0 [457.2]
48GP060090/115/130
208/230-1-60,
208/230-3-60,
460-3-60
468 212.3 42.98 [1091.7] 23.5 [596.9] 16.3 [412.8] 17.6 [447.0]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
in. [mm]
EVAP. COIL ACCESS SIDE..............................................................36.00 [914.0]
POWER ENTRY SIDE......................................................................36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .........................................................................................36.00 [914.0]
SIDE OPPOSITE DUCTS ................................................................36.00 [914.0]
DUCT PANEL ...................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
in. [mm]
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT.............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
MILLIMETERS [IN.]
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ...36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
FLUE HOOD
5