APPENDIX A — LOCAL DISPLAY AND CCN TABLES
MODE — RUN STATUS (cont)
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN WRITE
STATUS
ECON Economizer Status ECONDISP
EC.CP Econo Commanded Position xxx % ECONOCMD
EC.AP Econo Actual Position xxx % ECONOPOS
EC.MP MinPositioninEffect xxx % MIN_POS forcible
IAQ.S IAQ Level (switch) Low/High IAQIN
IAQ IAQ Level (sensor) xxxx IAQ
OAT Outdoor Air Temperature xxx.x _F OA_TEMP
RAT Return Air Temperature xxx.x _F RETURN_T
ENTH Outdoor Enthalpy Switch Low/High ENTHALPY
OAQ OAQ Level (sensor) xxxx OAQ
PE.1 Power Exhaust 1 Relay Off/On PE_1
PE.2 Power Exhaust 2 Relay Off/On PE_2
S.VFD SUPPLY FAN VFD VFD_DATA
VFD1 Status W ord 1 NNNNN VFD1STAT
SPD VFD1 Actual Speed % NNN.n % VFD1_SPD
RPM VFD1 Actual Motor RPM NNNNN VFD1RPM
FREQ VFD1 Actual Motor Freq NNN.n VFD1FREQ
AMPS VFD1 Actual Motor Amps NNN.n amps VFD1AMPS
TORQ VFD1 Actual Motor Torque NNNN.n % VFD1TORQ
PWR VFD1 Actual Motor Power NNNN.nn VFD1PWR
VDC VFD1 DC Bus Voltage NNNN volts VFD1VDC
V.OUT VFD1 Output Voltage NNNN volts VFD1VOUT
TEMP VFD1 Transistor Temp (C) NNN VFD1TEMP
RUN.T VFD1 Cumulative Run Time NNNNN hours VFD1RUNT
KWH VFD1 Cumulative kWh NNNNN VFD1KWH
LFC VFD1 Last Fault Code NNNNN VFD1LFC
(CCN Points Only) VFD1 DI1 State Open/Close VFD1_DI1
VFD1 DI2 State Open/Close VFD1_DI2
VFD1 DI3 State Open/Close VFD1_DI3
VFD1 DI4 State Open/Close VFD1_DI4
VFD1 DI5 State Open/Close VFD1_DI5
VFD1 DI6 State Open/Close VFD1_DI6
VFD1 AI1 (% of range) NNN.n % VFD1_AI1
VFD1 AI2 (% of range) NNN.n % VFD1_AI2
OAU Outside Air Unit Status OAUDISP
OA.RN OAU System Run State
1=AUTO
2=OFF
3=TEST
OAU_RUN
OA.OP OAU Operating Mode
0=Off
1=ERV (DCV)
2=Free Cooling
3=OA Tempering
4=Defrost
5=Test
6=Ext. Mode 1
7=Ext. Mode 2
8=Ext. Mode 3
OAU_MODE
UPC UPC Software Version xxxx UPC_VER
OAU OA Unit Software Version xxxx OAU_VER
2P.DM O A U 2 --- p o s i t i o n D a m p e r Close/Open OAUDMPR
WHL OAU Wheel Speed xxx % OAUWHEEL
LAT OAU Leaving Air Temp xxx.x _F OAU_LAT
EXAT OAU Exhaust Air Temp xxx.x _F OAU_EXAT
OA.MN Minimum Outside Air CFM xxxxx CFM MINOACFM
DCV.M Min DCV Outside Air CFM xxxxx CFM MINDCVSP
OA.FS OAU OA Fan Speed xxx % OAFANSPD
A.OA Actual Outside Air CFM xxxxx CFM ACTOACFM
C.OA Command Outside Air CFM xxxxx CFM CMDOACFM
PE.OF Power Exhaust CFM Offset xxxxx CFM EXOFFSET
EX.FS OAU Exhaust Fan Speed xxx % OAUPESPD
A.EX Actual Exhaust Air CFM xxxxx CFM ACTEXCFM
C.EX Command Exhaust Air CFM xxxxx CFM CMDEXCFM
BP.SP Building Pressure Setpnt x.xx in H2O OAU_BPSP
BP Building Pressure x.xx in H2O OAU_BP
TM.LO OA Tempring Lockout Temp xx _F OATMPL OC
TM.SP OA Tempring SAT Setpoint xx _F OATMPSPT
OA.HT OAU Tempering Heat er xxx % OAHEATER
HRS Component Run Hours STRTHOUR
A1 Compressor A1 Run Hours xxxxx.xx hours HR_A1 forcible
B1 Compressor B1 Run Hours xxxxx.xx hours HR_B1 forcible
IDF1 Indoor Fan 1 Run Hours xxxxx.xx hours HR_IDF1 forcible
IDF2 Indoor Fan 2 Run Hours xxxxx.xx hours HR_IDF2 forcible
IDF3 Indoor Fan 3 Run Hours xxxxx.xx hours HR_IDF3 forcible
HT.1 Heat Stage 1 Run Hours xxxxx.xx hours HR_HTR_1 forcible
HT.2 Heat Stage 2 Run Hours xxxxx.xx hours HR_HTR_2 forcible
PE.1 Power Exhaust1 Run Hours xxxxx.xx hours HR_PE_1 forcible
PE.2 Power Exhaust2 Run Hours xxxxx.xx hours HR_PE_2 forcible
ALRM Alarm Relay Run Hours xxxxx.xx hours HR_ALM forcible
CRC Reheat1 Valve Run Hours xxxxx.xx hours HR_CRC forcible
RH2.A Reheat2 Valve A Run Hrs xxxxx.xx hours HR_RH2_A forcible
RH2.B Reheat2 Valve BC Run Hrs xxxxx.xx hours HR_RH2_B forcible
ComfortLINK v1.X