Table 16 — “Configuration” Mode and Submode Directory
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
UNIT
Unit Configuration
U.CTL X Unit Control Type
Default: 1
1 = Auto Select
2 = Thermostat
3 = Space Sensor
T.CTL X Thermostat Control Type
Default: 0
0 = Adaptive
1 = 1 Stage Y1
2 = 2 Stage Y1
OC.FN YES/NO Fan On When Occupied Default: YES
S.DLY XXX Start Up Delay Default: 30 sec
IDF.F YES/NO Shut Down On IDF Failure Default: YES
FN.SW X Fan Status Input
Default: 0
0 = No Switch
1 = Normal Open
2 = Normal Close
FL.SW X Filter Status Input
Default: 0
0 = No Switch
1 = Normal Open
2 = Normal Close
FS.SW X Fire Shutdown Input
Default: 0
0 = No Switch
1 = Normal Open
2 = Normal Close
RM.SW X Remote Occupancy Switch
Default: 0
0 = No Switch
1 = Normal Open
2 = Normal Close
ECB YES/NO ECB Installed Default: YES
SAT.T XXX SAT Settling Time (Secs) Default: 240 sec
COOL
Cooling Configuration
N.CMP X Number of Compressors Default: 3 (016-024), 2 (014,028)
MC.LO XX Compressor Lockout Temp Default: 0° F
MRT.C XXX Compressor Min On Time Default: 180 sec
MOT.C XXX Compressor Min Off Time Default: 300 sec
CL.PD X.X SPT Cool Demand(+) Level Default: 1.0
∆
F
CL.ND X.X SPT Cool Demand (–) Level Default: –1.0
∆
F
C.LAG X.X Cool Thermal Lag Factor Default: 1.0 min
SA.PD X.X SAT Cool Demand (+) Level Default: 1.0
∆
F
SA.ND X.X SAT Cool Demand (–) Level Default: –1.0
∆
F
C.INC XXX Cool Stage Increase Secs Default: 450 sec
C.DEC XXX Cool Stage Decrease Secs Default: 300 sec
A.NOW YES/NO Alert Each Strike Default: YES
INV.E YES/NO Invert Evaporators Default: YES
A1.CS YES/NO A1 Current Sensing Default: YES
B1.CS YES/NO B1 Current Sensing Default: YES
C1.CS YES/NO C1 Current Sensing Default: YES