18
Table 16 — “Configuration” Mode and Submode Directory (cont)
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
HEAT Heating Configuration
HT.TY X Type of Heat Installed
Default: 0
0: No Heat
1: Gas
2: Electric
N.HTR X Number of Heat Stages Default: 2
HT.LO XX Heating Lockout Temp Default: 75 F
MRT.H XXX Heat Minimum On Time Default: 120 sec
MOT.H XXX Heat Minimum Off Time Default: 120 sec
HT.PD X.X SPT Heat Demand (+) Level Default: 1.0
∆
F
HT.ND X.X SPT Heat Demand (–) Level Default: –1.0
∆
F
H.LAG X.X Heat Thermal Lag Factor Default: 1.0 min
H.INC XXX Heat Stage Increase Secs Default: 450 sec
H.DEC XXX Heat Stage Decrease Secs Default: 300 sec
ECON Economizer Configuration
EC.EQ YES/NO Economizer Equipped Unit Default: NO
MIN.P XXX Economizer Min Position Default: 30 %
ECL.H XX Econ High Temp Lockout Default: 65 F
ECL.L XX Econ Low Temp Lockout Default: 0° F
FC.EN YES/NO Unoccupied Free Cooling Default: Yes
EN.SW X Enthalpy Switch Input
Default: 0
0: No Switch
1: Normal Open
2: Normal Close
PE.EN YES/NO Power Exhaust Control Default: NO
PE1.P XXX PE Stage1 Econo Position Default: 25 %
PE2.P XXX PE Stage2 Econo Position Default: 75 %
IAQ IAQ Configuration
AQ.MP XXX Minimum IAQ Position Default: 10 %
MIN.P XXX Economizer Min Position Default: 30 %
AQD.L XXX AQ Differential Low Default: 100 PPM
AQD.H XXXX AQ Differential High Default: 700 PPM
I.4M XXXX IAQ Sensor Value at 4MA Default: 0 PPM
I.20M XXXX IAQ Sensor Value at 20MA Default: 2000 PPM
O.4M XXXX OAQ Sensor Value at 4MA Default: 0 PPM
O.20M XXXX OAQ Sensor Value at 20MA Default: 2000 PPM
OAQ.L XXXX OAQ Lockout Value Default: 600 PPM
CCN CCN Configuration
CCN.A XXX CCN Address
Default: 1
Range: 1 to 239
CCN.B XXX CCN Bus Number
Default: 0
Range: 1 to 239
BAUD X CCN Baud Rate
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
B.TIM ON/OFF CCN Time/Date Broadcast Default: OFF
B.OAT ON/OFF CCN OAT Broadcast Default: OFF
B.GS ON/OFF Global Schedule Broadcast Default: OFF
B.ACK ON/OFF CCN Broadcast Ack’RDefault: OFF
ENTER
ENTER
ENTER
ENTER