19
Table 16 Configuration Mode and Submode Directory (cont)
LEGEND
Table 17 Example of Changing the CCN Configuration
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
DISP Display Configuration
METR YES/NO Metric Display
Default: NO
YES = Metric
NO = English
LANG X Language Selection
Default: 0
0 = English
1 = Espanol
2 = Francais
3 = Portuguese
PROT ENBL/DSBL Password Protection Default = Disabled
PSWD XXXX User Password Default = 1111
TEST ON/OFF Test Display LEDs
ALRM
Alarm Output Control
A.SPT YES/NO Space Sensor Failure Default: YES
A.SAT YES/NO SAT Thermistor Failure Default: YES
A.OAT YES/NO OAT Thermistor Failure Default: YES
A.CS YES/NO Current Sensor Failure Default: YES
A.CMP YES/NO Compressor Failure Default: YES
A.CKT YES/NO Refrig Circuit Failure Default: YES
A.SSP YES/NO SSP Transducer Failure Default: YES
A.SCT YES/NO SCT Thermistor Failure Default: YES
A.FAN YES/NO Indoor Fan Failure Default: YES
A.FIL YES/NO Plugged Filter Default: YES
A.TST YES/NO Thermostat Failure Default: YES
A.ECO YES/NO Economizer Failure Default: YES
AQ
Air Quality
OAT
Outdoor-Air Temperature
CCN
Carrier Comfort Network
PE
Power Exhaust
ECB
EconoMi$er Control Board
SAT
Supply Air Temperature
IAQ
Indoor-Air Quality
SCT
Saturated Condensing Temperature
OAQ
Outdoor-Air Quality
SPT
Space Temperature
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
CCN
CCN.A 1 CCN Address Default: 1
1 Scrolling Stops
Value flashes
Select 2
Change accepted
CCN.A Item/Value/Units scroll again
CCN.B CCN Bus Number No change
BAUD CCN Baud Rate Default: 3 = 9600
3 Scrolling Stops
3 Value flashes
Select 5 = 38,400
5 Change accepted
BAUD 5 CCN Baud Rate Item/Value/Units scroll again
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE