Table E — Inputs Main Menu Layout
DISPLAY EXPANDED TEXT VALUES UNITS WRITE STATUS POINT
INPUTS Inputs Menu
TEMPERATURES Temperatures Menu
SUPPLY AIR TEMP Supply Air Temperature xxx.x °F SAT
OUTDOOR AIR TEMP Outdoor Air Temperature xxx.x °F Forcible OAT
RETURN AIR TEMP Return Air Temperature xxx.x °F Forcible RAT
SPACE TEMPERATURE Space Temperature xxx.x °F Forcible SPACE_T
SLIDER OFFSET VAL Space Temperature Offset xx.x °F Forcible SPTO
CIR.A SUC TEMP Cir.A Sat.Suction Temp xxx.x °F SST_A
CIR.A DIS. TEMP Cir.A Sat.Discharge Temp xxx.x °F SDT_A
FAN SUPPLY TEMP Fan Supply Air Temp xxx.x °F FST
PRESSURES Pressures Menu
CIR.A SUC. PRESS Cir.A Suction Pressure xxx.x psig SSP_A
CIR.A DIS. PRESS Cir.A Discharge Pressure xxx.x psig SDP_A
CIR.A PRESS RATIO Circuit A Pressure Ratio xxx.x CIRA_PR
BAROMETRIC PRESS Barometric Pressure xxx.x in. Hg Forcible BARP
THERMOSTAT Thermostat Inputs Menu
TSTAT G INPUT Thermostat G Input On/Off Forcible G
TSTAT Y1 INPUT Thermostat Y1 Input On/Off Forcible Y1
TSTAT Y2 INPUT Thermostat Y2 Input On/Off Forcible Y2
TSTAT Y3 INPUT Thermostat Y3 Input On/Off Forcible Y3
TSTAT W1 INPUT Thermostat W1 Input On/Off Forcible W1
TSTAT W2 INPUT Thermostat W2 Input On/Off Forcible W2
SWITCH INPUTS Switch Inputs Menu
IGC FAN REQUEST IGC Fan On Request (IFO) On/Off Forcible IGC_IFO
CIR.A HPS Cir.A High Pressure Sw Open/Close Forcible CIRA_HPS
HUMIDISTAT Humidistat I/P On/Off Forcible HUMDSTAT
FIRE SHUTDOWN Fire Shutdown Switch Alarm/Normal Forcible FIREDOWN
COFS COFS Switch State High/Low Forcible COFS
FILTER STATUS SW Filter Status Switch Dirty/Clean Forcible FILTSTAT
REMOTE OCC SWITCH Remote Occupancy Switch On/Off Forcible REMOCC
REMOTE SHUTDOWN Remote Shutdown Switch On/Off Forcible REMSHUT
GENERAL STATUS SW General Status Switch Alarm/Normal Forcible GENSTAT
ENTHALPY SWITCH Enthalpy Switch High/Low Forcible ENTH_SW
ANALOG INPUTS Analog Inputs Menu
ECON ACT POSITION Econo Actual Position 0 to 100 % DAMPPOS
SPRH LEVEL Space RH 0 to 100 % Forcible SPRH
OARH LEVEL OA Relative Humidity 0 to 100 % Forcible OARH
RARH LEVEL RA Relative Humidity 0 to 100 % Forcible RARH
IAQ LEVEL Indoor Air Quality Level xxxx ppm Forcible IAQ
OAQ LEVEL OA Quality Level xxxx ppm Forcible OAQ
OUTDOOR AIR CFM Outdoor Air in CFM xxx.x CFM Forcible OACFM
GENERAL INPUTS General Inputs Menu
FILTER TIME LEFT Filter Hour Remaining xxxx hours FILTLEFT
RESET FILTER TIME Reset Filter Timer Yes/No Command RESETFLT
OUTDOOR ENTHALPY Outdoor Air Enthalpy xxx.x Btu/lb Forcible OA_ENTH
RETURN ENTHALPY Return Air Enthalpy xxx.x Btu/lb Forcible RA_ENTH
DIFF AIR QUALITY Differential Air Quality xxxx ppm AQ_DIFF
INDOOR FAN VFD DATA Indoor Fan VFD Data
IDF VFD RUN HOURS IDF VFD Motor Run Hours xxxxxxxx hours VFDMHOUR
IDF VFD KW HOURS IDF VFD Cumulative kWh xxxxx kWh KWHCNTR
VFD REF SPEED IDF VFD Reference Speed 0 to 1000 % REFSPEED
VFD STATUS WORD IDF VFD Status Word xxxxxxxx VFD1STSW
IDF VFD FEEDBACK IDF VFD Actual Speed % xxxxx % MAV
VFD OUTPUT KW IDF VFD Output Power kW 0 to 1000 kWh OUTPWRKW
VFD OUTPUT HP IDF VFD Output Power HP 0 to 1000 HP OUTPWRHP
VFD OUTPUT VOLTS IDF VFD Output Voltage xxxxx volts OUTMVOLT
VFD OUTPUT FREQ IDF VFD Output Freq. xxxxx.x Hz OUTMFREQ
VFD OUTPUT AMPS IDF VFD Output Amps xxx.xx amps OUTMCUR
IDF VFD DC VOLTS IDF VFD DC Bus Voltage xxx volts DCLNVOLT
IDF VFD HSNK TEMP IDF VFD Heatsink Temp xxx.x °F HTSINKT
IDF VFD ALM WORD IDF VFD Alarm Word xxxxxxxx ALMERRC