112
GENERAL INPUTS (cont)
VFD FAULT DETAIL IDF VFD Fault Detail
0=NONE,
1=PWR CARD,
2=EARTH FLT,
3=CTRL WORD,
4=OVER CURR,
5=OVER TEMP,
6=OVERLOAD,
7=UNDERVOLT,
8=OVER VOLT,
9=SHORT CIR,
10=PHASELOSS,
11=U LOSS,
12=V LOSS,
13=W LOSS,
14=CTRL VOLT,
15=VDD LOW,
16=MULTIPLE,
17=UNEXPECT
SVFDFLT
VFD WARN DETAIL IDF VFD Warning Detail
0=NONE,
1=VOLTAGE,
2=CURRENT,
3=THERMAL,
4=MULTIPLE,
5=UNEXPECT
SVFDWAR
NETWORK Network Menu
BMS OCC REQUEST BMS Occupancy Request
0=UNOCC,
1=OCCUPIED,
2=DISABLED
Forcible BMS_OCC
LINKAGE OCC REQ Linkage Occupied Request
0=Unocc,
1=Occupied,
2=Disabled
LNK_OCC
OAT NETWORK VALUE Network OAT Value xxx.x °F OAT_NET
RAT NETWORK VALUE Network Return Air Temp xxx.x °F RAT_NET
SPT NETWORK VAL. Network Space Temp Value xxx.x °F SPT_NET
OARH NETWORK VAL. Network OARH Value 0 to 100 % OARH_NET
RARH NETWORK VAL. Network RARH Value 0 to 100 % RARH_NET
IAQ NETWORK VALUE Network IAQ Value xxxx ppm IAQ_NET
OAQ NETWORK VALUE Network OAQ Value xxxx ppm OAQ_NET
OACFM NETWORK VAL Network OACFM Value xxxx CFM OCFM_NET
ZS SENSOR INFO ZS Sensor Information
ZS SPACE TEMP Zone Sensor Temp Out –40 to 245 °F ZSZT
ZS SPACE RH Zone Sensor Humidity Out 0 to 100 % ZSSPRH
ZS SPOFFSET ZS Setpoint Offset Output –10 to 10 °F delta ZSSPTO
ZS OVER TIME LEFT ZS Override Time Remaining 0 to 600 min ZSOTR
ZS TEMPERATURE ZS Space Temperature
ZS1 TEMPERATURE Zone Sensor 1 Temp –40 to 245 °F ZS1ZT
ZS2 TEMPERATURE ZS2 Temperature –40 to 245 °F ZS2ZT
ZS3 TEMPERATURE ZS3 Temperature –40 to 245 °F ZS3ZT
ZS4 TEMPERATURE ZS4 Temperature –40 to 245 °F ZS4ZT
ZS5 TEMPERATURE ZS5 Temperature –40 to 245 °F ZS5ZT
ZS HUMIDITY ZS Space Humidity
ZS1 HUMIDITY ZS1 Humidity 0 to 100 % ZS1ZHUM
ZS2 HUMIDITY ZS2 Humidity 0 to 100 % ZS2ZHUM
ZS3 HUMIDITY ZS3 Humidity 0 to 100 % ZS3ZHUM
ZS4 HUMIDITY ZS4 Humidity 0 to 100 % ZS4ZHUM
ZS5 HUMIDITY ZS5 Humidity 0 to 100 % ZS5ZHUM
ZS CSP OFFSET ZS Cool Setpoint Offset
ZS1 CSP OFFSET ZS1 Cool Setpoint Offset –10 to 10 °F delta ZS1CSOFF
ZS2 CSP OFFSET ZS2 Cool Setpoint Offset –10 to 10 °F delta ZS2CSOFF
ZS3 CSP OFFSET ZS3 Cool Setpoint Offset –10 to 10 °F delta ZS3CSOFF
ZS4 CSP OFFSET ZS4 Cool Setpoint Offset –10 to 10 °F delta ZS4CSOFF
ZS5 CSP OFFSET ZS5 Cool Setpoint Offset –10 to 10 °F delta ZS5CSOFF
ZS HSP OFFSET ZS Heat Setpoint Offset
ZS1 HSP OFFSET ZS1 Heat Setpoint Offset –10 to 10 °F delta ZS1HSOFF
ZS2 HSP OFFSET ZS2 Heat Setpoint Offset –10 to 10 °F delta ZS2HSOFF
ZS3 HSP OFFSET ZS3 Heat Setpoint Offset –10 to 10 °F delta ZS3HSOFF
ZS4 HSP OFFSET ZS4 Heat Setpoint Offset –10 to 10 °F delta ZS4HSOFF
ZS5 HSP OFFSET ZS5 Heat Setpoint Offset –10 to 10 °F delta ZS5HSOFF
Table E — Inputs Main Menu Layout (cont)
DISPLAY EXPANDED TEXT VALUES UNITS WRITE STATUS POINT
APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY