133
COOLDISP
OK to Use Free Cooling? Yes/No OKFREECL
Free Cooling Active Yes/No FREECOOL
Free Cooling SAT Setpnt xx.x °F FC_SATSP
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
Commanded IDF Speed 0 to 100 % FANSPEED
Ok to use compressors? Yes/No OKMECHCL
Mechanical Cool active? Yes/No MECHCOOL
Max Allowed Cool Stages 0 to 3 MAXCSTGS
Requested Cooling Stages 0 to 3 REQCSTGS
Actual Cool Stage Active x ACTCSTGS
Circuit A Compressor 1 On/Off COMP_A1
Circuit A Compressor 2 On/Off COMP_A2
Circuit A CMP A1 Loader On/Off COMP_ALD
Compressor A1 Timeguard xxx sec TIMGD_A1
Compressor A2 Timeguard xxx sec TIMGD_A2
cmp Loader Timeguard xxx sec TIMG_ALD
Commanded ODF Speed xxxx rpm ODFSPD
OK to use humidimizer Yes/No OKTOHUMZ
Requested Dehum Level 0 to 2 REQDHLEV
Req Compr Dehum Stgs 0 to 3 rpm REQDSTGS
Cir.A Sat.Discharge Temp xxx.x °F SDT_A
Cir.A Sat.Suction Temp xxx.x °F SST_A
Cir.A Discharge Pressure xxx.x psig SDP_A
Cir.A Suction Pressure xxx.x psig SSP_A
Circuit A Pressure Ratio xx.xx CIRA_PR
Cir.A High Pressure Sw Open/Close CIRA_HPS
Supply Air Temperature xxx.x °F SAT
Outdoor Air Temperature xxx.x °F OAT Forcible
HEATDISP
OK to Run Heat Yes/No OKTOHEAT
OK to Supply Air Tempering Yes/No OKTOTEMP
IGC Fan On Request (IFO) On/Off IGC_IFO
Commanded IDF Speed 0 to 100 % FANSPEED
Max Allowed Heat Stages 0 to 2 MAXHSTGS Forcible
Requested Heating Stages 0 to 2 REQHSTGS
Actual Heat Stage Active x ACTHSTGS
Heat Stage 1 Relay On/Off HEAT_1
Heat Stage 2 Relay On/Off HEAT_2
Heat Stage 1 Timeguard xxx sec TIMGD_H1
Heat Stage 2 Timeguard xxx sec TIMGD_H2
VENTDISP
Ventilation Status see Appendix B VENTSTAT
Ventilation Status see Appendix B VENTTEXT
Min Position in Effect 0 to 100 % MIN_POS Forcible
In Pre-Occupancy Purge? Yes/No PREOCCON
Differential Air Quality xxxx ppm AQ_DIFF
Commanded IDF Speed 0 to 100 % FANSPEED
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
Econo Actual Position 0 to 100 % DAMPPOS Forcible
Free Cooling active Yes/No FREECOOL
Currently Occupied Yes/No OCCUPIED Forcible
Mins until next occupied xxxxx min MINTILOC
Ok to Preoccupancy Purge Yes/No OKPREOCC
Power Exhaust 1 Relay On/Off PE1 Forcible
Power Exhaust 2 Relay On/Off PE2 Forcible
ALRMDISP
Active Alarm 1 Code xxx ALMCODE1
Active Alarm 2 Code xxx ALMCODE2
Active Alarm 3 Code xxx ALMCODE3
Active Alarm 4 Code xxx ALMCODE4
Active Alarm 5 Code xxx ALMCODE5
Reset All Current Alarms Yes/No ALRESET Writable
Table S — Status Display Tables (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES