Table T — MAINTENANCE TABLES
TABLE DISPLAY NAME RANGE UNITS POINT NAME
WRITE
STATUS
MODES
Operating Mode see Appendix B MODETEXT
System Mode see Appendix B SYSMODE
Operating Sub-Mode see Appendix B SUBMTEXT
Running Mode Operation see Appendix B SUB_MODE
Ventilation Status see Appendix B VENTTEXT
Ventilation Status see Appendix B VENTSTAT
System Demand see Appendix B SYS_DMDT
System Demand 0 to 99 SYS_DMD
Currently Occupied Yes/No OCCUPIED Forcible
Linkage Active Yes/No LNK_ACT Forcible
Unocc Free Cool Active Yes/No UFC_ACT
Temp Compensate Start On Yes/No TCS_ACT
Current Mode Ended Yes/No MODEDONE
Cool Mode Select T.guard xxx sec COOLMSTG
Heat Mode Select T.guard xxx sec HEATMSTG
Cool Setpoint In Effect xx.x °F CSP_EFF
Heat Setpoint In Effect xx.x °F HSP_EFF
Effective Demand Temp xxx.x °F TEMP_EFF
Space Cooling Demand xx.x °F COOL_DMD
Cooling Demand Trend xx.x ^F/min CLDTREND
Heating Space Demand xx.x °F HEAT_DMD
Heat Space Demand Trend xx.x ^F/min HTDTREND
TESTMODE
Economizer Position Test 0 to 100 % S_DAMPER
Compressor Bump A1 Test On/Off S_BMPA1
Compressor Bump A2 Test On/Off S_BMPA2
Cmp Bump Loader Test On/Off S_BMPALD
Liq Diverter Val Rly Tst On/Off S_LDV_A
Rht Dischg Valve Rly Tst On/Off S_RDV_A
Reheat Liq Valv Rly Test On/Off S_RLV_A
Cooling Liq Valv Test On/Off S_CLV_A
Crankcase Heater 1 Test On/Off S_CCHR1
Alarm Output Relay Test On/Off S_ALARM
Power Exhaust 1 Test On/Off S_PE_1
Power Exhaust 2 Test On/Off S_PE_2
Indoor Fan Speed Test 0 to 100 % S_IDFSPD
System ODF Speed Test 0 to 1200 rpm S_ODFSPD
Outdoor Fan 1 Speed Test 0 to 1200 rpm S_ODFSP1
Outdoor Fan 2 Speed Test 0 to 1200 rpm S_ODFSP2
Outdoor Fan 3 Speed Test 0 to 1200 rpm S_ODFSP3
IDF Manual Transition Yes/No S_IDFTRN
ODF Manual Transition Yes/No S_ODFTRN
Cooling W/Comp.A1 Test On/Off S_COOLA1
Cooling W/Comp.A2 Test On/Off S_COOLA2
Cooling W/Comp.ALD Test On/Off S_COLALD
HumidiMizer Level
0=Off,
1=Subcool,
2=Reheat
S_HMZLEV
Heating Stage 1 Test On/Off S_HEAT1
Heating Stage 2 Test On/Off S_HEAT2
AUTO INDEPENDENT TEST Yes/No AUTOINDP
RUN AUTO COOLING TEST Yes/No AUTOCOOL
RUN AUTO HEATING TEST Yes/No AUTOHEAT
RUN AUTO SYSTEM TEST Yes/No AUTOSYS
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES