140
HEATDIAG
System Demand see Appendix B SYS_DMDT
Operating Sub-Mode see Appendix B SUBMTEXT
IGC Fan On Request (IFO) On/Off IGC_IFO
Requested IDF Speed 0 to 100 % RQFANSPD
Commanded IDF Speed 0 to 100 % FANSPEED
OK to Run Heat Yes/No OKTOHEAT
All Heat Stages Lockout Yes/No ALLHTLOC Forcible
Max Allowed Heat Stages 0 to 2 MAXHSTGS Forcible
Supply Air Temp Trend xxx.x ^F/min SATTREND
Supply Air Temperature xxx.x °F SAT
Requested Heating Stages 0 to 2 REQHSTGS
Heat Stage 1 Timeguard xxx sec TIMGD_H1
Heat Stage 2 Timeguard xxx sec TIMGD_H2
Heat Stage 1 Available Yes/No HT1_AVAL
Heat Stage 2 Available Yes/No HT2_AVAL
Heat Stage 1 Relay On/Off HEAT_1
Heat Stage 2 Relay On/Off HEAT_2
Actual Heat Stage Active x ACTHSTGS
Outdoor Air Temperature xxx.x °F OAT Forcible
Return Air Temperature xxx.x °F RAT Forcible
Fan Supply Air Temp xxx.x °F FST
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
PE_DIAG
0 =None
1 =MBB RLY11
2 =MBB RLY06
PE1 Relay Channel 0 to 2 PE1_CHAN
PE2 Relay Channel 0 to 2 PE2_CHAN
PE Turn Off Deadband 0 to 100 % PE_OFFDB
Power Exhaust 1 Relay On/Off PE1 Forcible
Power Exhaust 2 Relay On/Off PE2 Forcible
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
Commanded IDF Speed 0 to 100 % FANSPEED
P.Exhaust 1 Curve Offset 0 to 100 % PE1_OFFS
P.Exhaust 2 Curve Offset 0 to 100 % PE2_OFFS
IDF Maximum Fan Speed 80 to 100 % SPEEDMAX
Power Exhaust 1 - Speed1 0 to 100 % PE1_SPD1
Power Exhaust 1 - Speed2 0 to 100 % PE1_SPD2
Power Exhaust 1 - Speed3 0 to 100 % PE1_SPD3
PE Stage 1 at Max speed 0 to 100 % PE1_PMAX
Power Exhaust 1 - Pos 1 0 to 100 % PE1_POS1
Power Exhaust 1 - Pos 2 0 to 100 % PE1_POS2
Power Exhaust 1 - Pos 3 0 to 100 % PE1_POS3
IDF Maximum Fan Speed 80 to 100 % SPEEDMAX
Power Exhaust 2 - Speed1 0 to 100 % PE2_SPD1
Power Exhaust 2 - Speed2 0 to 100 % PE2_SPD2
Power Exhaust 2 - Speed3 0 to 100 % PE2_SPD3
PE Stage 2 at max speed 0 to 100 % PE2_PMAX
Power Exhaust 2 - Pos 1 0 to 100 % PE2_POS1
Power Exhaust 2 - Pos 2 0 to 100 % PE2_POS2
Power Exhaust 2 - Pos 3 0 to 100 % PE2_POS3
VENTDIAG
Operating Sub-Mode see Appendix B SUBMTEXT
Ventilation Status see Appendix B VENTTEXT
Ventilation Status see Appendix B VENTSTAT
Currently Occupied Yes/No OCCUPIED Forcible
Table T — MAINTENANCE TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME
WRITE
STATUS
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES