VENTDIAG
(cont)
Mins until next occupied xxxxx min MINTILOC
Fan On When Occupied Yes/No FANON_OC
Commanded IDF Speed 0 to 100 % FANSPEED
Free Cooling Active Yes/No FREECOOL
Min Position in Effect 0 to 100 % MIN_POS Forcible
Requested Damper Pos 0 to 100 % REQDAMP
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
Econo Actual Position 0 to 100 % DAMPPOS Forcible
Analog Input IAQ Control
0=NO IAQ,
1=DCV,
2=IAQ OVRD,
3=CTRL MINP
IAQANCFG
Indoor Air Quality Level xxxx PPM IAQ Forcible
OA Quality Level xxxx PPM OAQ Forcible
Differential Air Quality xxxx PPM AQ_DIFF
AQ Differential High xxxx PPM DAQ_HIGH
AQ Differential Low xxxx PPM DAQ_LOW
AQ Diff High IAQOVERRIDE 0 to 5000 PPM AQD_HIGH
AQ Diff Low- IAQ OVERRIDE 0 to 5000 PPM AQD_LOW
IAQ Override Enable Yes/No IAQOVREN
IAQ Preoccupancy Purge Yes/No IAQPURGE
Preocc Purge Lockout OAT 0 to 70 °F IAQP_LA
Ok to Preoccupancy Purge Yes/No OKPREOCC
Preocc Purge Duration 5 to 120 min IAQPTIME
In Pre-Occupancy Purge? Yes/No PREOCCON
Is IAQ Override Active? Yes/No IAQ_OVRD
IAQ override sw state Yes/No IAQ_OVRS
Economizer Installed? Yes/No ECONO
Commanded IDF Speed 0 to 100 % FANSPEED
Supply Air Temperature xxx.x °F SAT
Return Air Temperature xxx.x °F RAT Forcible
Outdoor Air Temperature xxx.x °F OAT Forcible
Damper SAT Deadband 0 to 20 °F T24SATDB
T24 Min Diff in RAT-OAT 5 to 20 °F T24RATDF
T24 Heat/Cool End Delay 0 to 60 min T24CHDLY
SAT Heat Mode Sensing Enable/Disable SAT_HEAT
Actual Heat Stage Active x ACTHSTGS
Actual Cool Stage Active x ACTCSTGS
OK to Use Free Cooling? Yes/No OKFREECL
T24 Test Minimum Pos 0 to 100 % T24TSTMN
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
T24 Test Maximum Pos 0 to 100 % T24TSTMX
T24 Econ Min Move for SAT 10 to 20 % T24ECSTS
Econo Actual Position 0 to 100 % DAMPPOS Forcible
IAQODIAG
AQ Diff High IAQOVERRIDE 0 to 5000 PPM AQD_HIGH
AQ Diff Low-IAQ OVERRIDE 0 to 5000 PPM AQD_LOW
IAQ override enable Yes/No IAQOVREN
Is IAQ Override Active? Yes/No IAQ_OVRD
IAQ override sw state Yes/No IAQ_OVRS
VENTCURV
Econ Min at Max Fanspeed 0 to 100 % MINP_MAX
Min Pos - User Pos 1 0 to 100 % MP_UPOS1
Min Pos - User Pos 2 0 to 100 % MP_UPOS2
Min Pos - User Pos 3 0 to 100 % MP_UPOS3
IDF Maximum Fan Speed 80 to 100 % SPEEDMAX
Min Pos - User Speed 1 0 to 100 % MP_USPD1
Min Pos - User Speed 2 0 to 100 % MP_USPD2
Table T — MAINTENANCE TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME
WRITE
STATUS
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES