HW_IO (cont)
Assigned S-AI01 Function
0 =None,
1 = IAQ,
2 =OARH,
3 = RARH,
4 =OAQ,
5 = SPRH,
6 =OACFM
SIOAI01F
Assigned DI02 Function
0 =None,
1 =COFS,
2 = REMOCC,
3 = REMOFF,
4 = Filter,
5 = Enthalpy
6 = General Status,
7 =Humidistat
MBBDI02F
Assigned DI04 Function
0 =None,
1 =COFS,
2 = REMOCC,
3 = REMOFF,
4 = Filter,
5 = Enthalpy
6 = General Status,
7 =Humidistat
MBBDI04F
Assigned DI12 Function
0 =None,
1 =COFS,
2 = REMOCC,
3 = REMOFF,
4 = Filter,
5 = Enthalpy
6 = General Status,
7 =Humidistat
MBBDI12F
Assigned DI12 Function
0 =None,
1 =COFS,
2 = REMOCC,
3 = REMOFF,
4 = Filter,
5 = Enthalpy
6 = General Status,
7 =Humidistat
MBBDI12F
Assigned DI13 Function
0 =None,
1 =COFS,
2 = REMOCC,
3 = REMOFF,
4 = Filter,
5 = Enthalpy
6 = General Status,
7 =Humidistat
MBBDI13F
Assigned DI14 Function
0 =None,
1 =COFS,
2 = REMOCC,
3 = REMOFF,
4 = Filter,
5 = Enthalpy
6 = General Status,
7 =Humidistat
MBBDI14F
Assigned S-DI01 Function
0 =None,
1 =COFS,
2 = REMOCC,
3 = REMOFF,
4 = Filter,
5 = Enthalpy
6 = General Status,
7 =Humidistat
SIODI01F
Assigned Rly 06 Function
0 =None,
1 = Alarm Relay,
2 = PE1
3 = PE2
MBBRY06F
Assigned Rly 11 Function
0 =None,
1 = Alarm Relay,
2 = PE1
3 = PE2
MBBRY11F
Outdoor Air Temp Sensor xxx.x °F OAT_LOC
Return Air Temp Sensor xxx.x °F RAT_LOC
Space Temperature Sensor xxx.x °F SPT_LOC
SPRH Sensor Value 0 to 100 % SPRH_LOC
Local Space Temp Offset xxxx °F delta SPTO_LOC
Table T — MAINTENANCE TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME
WRITE
STATUS