HW_IO
(cont)
OARH Sensor Value 0 to 100 % OARH_LOC
RARH Sensor Value 0 to 100 % RARH_LOC
IAQ Sensor Value xxxx ppm IAQ_LOC
OAQ Sensor Value xxxx ppm OAQ_LOC
OACFM Sensor Value xxx.x cfm OCFM_LOC
Equipment Model Number xxxxxxxxxxxxxxxxxx EQ_MOD
Equipment Serial Number xxxxxxxxxx EQ_SER
Application SW Version CESR131651-xx-xx FW_CESR
VFD1 SW Version text VFD1_SW
SIOB1 SW Version SIOB1 SW VERSION-xx-xx SIOB1_SW
Bootloader SW Version CESR131659-xx-xx BL_CESR
MBB Part Number CEPL131117-xx-R BD_CEPL
MBB Program Part Number CEPP130644-xx-xx-xx-R BD_CEPP
Base Board Serial Number xxxxNxxxxxx BD_SER
ZSENSORS
Zone Sensor Temp Out –40 to 245 °F ZSZT
ZS1 Temp –40 to 245 °F ZS1ZT
ZS2 Temperature –40 to 245 °F ZS2ZT
ZS3 Temperature –40 to 245 °F ZS3ZT
ZS4 Temperature –40 to 245 °F ZS4ZT
ZS5 Temperature –40 to 245 °F ZS5ZT
Zone Sensor Humidity Out 0 to 100 % ZSSPRH
ZS1 Humidity 0 to 100 % ZS1ZHUM
ZS2 Humidity 0 to 100 % ZS2ZHUM
ZS3 Humidity 0 to 100 % ZS3ZHUM
ZS4 Humidity 0 to 100 % ZS4ZHUM
ZS5 Humidity 0 to 100 % ZS5ZHUM
ZS Override Time Remain 0 to 600 min ZSOTR
ZS1 Override Time Remain 0 to 600 min ZS1OTR
ZS2 Override Time Remain 0 to 600 min ZS2OTR
ZS3 Override Time Remain 0 to 600 min ZS3OTR
ZS4 Override Time Remain 0 to 600 min ZS4OTR
ZS5 Override Time Remain 0 to 600 min ZS5OTR
ZS Setpoint Offset Output –10 to 10 °F delta ZSSPTO
ZS1 Cool Setpoint Offset –10 to 10 °F delta ZS1CSOFF
ZS2 Cool Setpoint Offset –10 to 10 °F delta ZS2CSOFF
ZS3 Cool Setpoint Offset –10 to 10 °F delta ZS3CSOFF
ZS4 Cool Setpoint Offset –10 to 10 °F delta ZS4CSOFF
ZS5 Cool Setpoint Offset –10 to 10 °F delta ZS5CSOFF
ZS1 Heat Setpoint Offset –10 to 10 °F delta ZS1HSOFF
ZS2 Heat Setpoint Offset –10 to 10 °F delta ZS2HSOFF
ZS3 Heat Setpoint Offset –10 to 10 °F delta ZS3HSOFF
ZS4 Heat Setpoint Offset –10 to 10 °F delta ZS4HSOFF
ZS5 Heat Setpoint Offset –10 to 10 °F delta ZS5HSOFF
USER_INS
Supply Voltage Leg 1 0 to 700 volt L1VOLTS
Supply Voltage Leg 2 0 to 700 volt L2VOLTS
Supply Voltage Leg 3 0 to 700 volt L3VOLTS
Comp A1 Amps Leg 1 0 to 100 amps CA1L1_A
Comp A1 Amps Leg 2 0 to 100 amps CA1L2_A
Comp A1 Amps Leg 3 0 to 100 amps CA1L3_A
Comp A2 Amps Leg 1 0 to 100 amps CA2L1_A
Comp A2 Amps Leg 2 0 to 100 amps CA2L2_A
Comp A2 Amps Leg 3 0 to 100 amps CA2L3_A
Elec. Heat Amps Leg 1 0 to 100 amps EHTL1_A
Elec. Heat Amps Leg 2 0 to 100 amps EHTL2_A
Elec. Heat Amps Leg 3 0 to 100 amps EHTL3_A
Gas Supply Type
0 =Natural,
1 = LP
GASTYPE
Table T — MAINTENANCE TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME
WRITE
STATUS