INPUTCFG
(cont)
Humidistat Switch Type
0 = Normally Open,
1 = Normally Closed
HUMD_CFG
Filter Status Switch Type
0 = Normally Open,
1 = Normally Closed
FILT_CFG 0=NORM OPEN
Remote Occupancy Sw Type
0 = Normally Open,
1 = Normally Closed
RMOC_CFG 0=NORM OPEN
Remote Shutdown Sw Type
0 = Normally Open,
1 = Normally Closed
ROFF_CFG 0=NORM OPEN
COFS Switch Type
0 = Normally Open,
1 = Normally Closed
COFS_CFG 1=NORM CLSD
General Status Sw Type
0 = Normally Open,
1 = Normally Closed
GENS_CFG 0=NORM OPEN
Enthalpy Switch Type
0 = Normally Open,
1 = Normally Closed
ENTH_CFG 0=NORM OPEN
IAQ Override Switch Type
0=NORM OPEN,
1=NORM CLSD
IAQOSCFG 0=NORM OPEN
General Status shutdown? Yes/No GENFATAL Yes
Remote Shutdown ALM Type
0=Normal,
1=Emergency
ROFFTYPE 0=Normal
Fire Shutdown Switch
0 =Normally Open,
1 =Normally Closed,
2 =No Switch
FIRE_CFG
2: no FIOP
0: FIOP
SPRH Sensor Value at 4mA 0 to 100 % SPRH_4MA
SPRH Sensor Value at 20mA 0 to 100 % SPRH20MA
IAQ Sensor Value at 4mA 0 to 5000 ppm IAQ_4MA 0
IAQ Sensor Value at 20mA 0 to 5000 ppm IAQ_20MA 2000
OAQ Sensor Value at 4mA 0 to 5000 ppm OAQ_4MA 0
OAQ Sensor Value at 20mA 0 to 5000 ppm OAQ_20MA 2000
OARH Sensor Value at 4mA 0 to 100 % OARH_4MA 0
OARH Sensor Val. at 20mA 0 to 100 % OARH20MA 100
RARH Sensor Value at 4mA 0 to 100 % RARH_4MA 0
RARH Sensor Value at 20mA 0 to 100 % RARH20MA 100
OACFM value at 4MA 0 to 100 cfm OCFM_4MA
OACFM Value at 20mA 0 to 100 cfm OCFM20MA
IDF_CFG
Indoor Fan Type
0=None,
1=VFD,
2=DIRECT DRIVE
IDFTYPE
1=VFD: all except Direct Drive
motor Option
2 = DIRECT DRIVE: on 04-06
size with direct drive motors
Number Of Fan Speeds 2 to 3 NUMFSPDS 2
Fan On When Occupied Yes/No FANON_OC Yes
IDF Maximum Fan Speed 80 to 100 % SPEEDMAX 100
Ventilation Only IDF Spd 0 to 100 % FSPDVENT
67 (sizes 07-12)
53 (sizes 14 or 20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
50 (sizes 04-06)
Heating IDF Speed 20 to 100 % FSPD_HT 100
Free Cooling IDF Speed 0 to 100 % FSPD_FCL
67 (sizes 07-12)
53 (sizes 14 or 20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
70 (size 04)
57 (sizes 05-06)
Low Cooling IDF Speed 20 to 100 % FSPD_LCL
67 (sizes 07-12)
53 (sizes 14 or 20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
70 (size 04)
57 (sizes 05-06)
Table U — SERVICE CONFIGURATION TABLES (cont)
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES