150
IDF_CFG
(cont)
Med Cooling IDF Speed 20 to 100 % FSPD_MCL
67 (sizes 07-12)
79 (sizes 14)
82 (sizes 17)
62 (sizes 20)
65 (sizes 24)
72 (sizes 26)
87 (sizes 04)
71 (sizes 05)
69 (sizes 06)
High Cooling IDF Speed 20 to 100 % FSPD_HCL 100
Shut Down on IDF Failure Yes/No FATALFAN Yes
VFD Hand Mode Shutdown? Yes/No HANDSHUT Yes
IDF VFD Motor In Reverse Yes/No VFD1MDIR
No (sizes 04-12)
Yes (sizes 14-26)
IDF Danfoss Min Ref 0 to 65 Hz MINREF 0
IDF Danfoss Max Ref 0 to 65 Hz MAXREF 60
IDF Danfoss Comm. TO 1 to 600 sec CNT_TOUT 30
IDF Danfoss Auto Reset 0 to 600 sec ARSTRT_T 30
IDF Danfoss RFI Filter On/Off RFIFILTR On
IDF ABB motor direction x VFDABBMD 2
IDF ABB Switching Freq. x VFD1SWFQ 2
IDF ABB Relay Cfg. x ABBRELAY 8
IDF ABB Ext. Relay Cfg. x ABBEXRLY 0
IDF ABB EXT 1 Commands x ABB_EXT1 2
IDF ABB EXT 1 Ref Select x ABB_EXTS 2
IDF ABB ConstSpeed 7 x Hz ABB_CSP7 0
IDF ABB Run Enable x VFDRUNEN 7
IDF ABB Start Enable 1 x VFDSTAEN 4
IDF ABB Fault Reset Sel x VFDFLTRE 7
IDF ABB Start Function x VFDSTAFN 0
IDF ABB Stop Function x VFDSTPFN 1
IDF ABB Stall Function x VFDSTLFN 2
IDF ABB Stall Time x sec VFDSTLTM 10
IDF VFD Motor Volts 50 to 1000 volts MOTVOLT
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
IDF VFD Motor HP 1 to 26 horsepower MOTPWRHP
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
IDF VFD Motor Freq. 20 to 400 Hz MOTFREQ 60
IDF VFD Motor Current 0.1 to 40 Amps MOTCUR
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
IDF VFD Max Current 0 to 655.35 Amps VFD1MAXA
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
IDF VFD Motor Nom. RPM 100 to 60000 rpm MOTNOMSP
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
IDF VFD Accel. Time 1 to 1800 sec RAMPUP_T 10
IDF VFD Decel. Time 1 to 1800 sec RAMPDN_T 10
COOL_CFG
Low Cool Compressor 1 to 2 LC_COMP 1
1 = Compressor A1
2 = Compressor A2
Compressor Min On Time 180 to 600 sec C_MINON 300
Compressor Min Off Time 120 to 600 sec C_MINOFF 180
Runtime to Reset Strikes 120 to 999 sec MIN_ON_S 300
Cool Stage Increase Time 120 to 999 sec CSTAGINC 450
Table U — SERVICE CONFIGURATION TABLES (cont)
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES