COOL_CFG
(cont)
Cooling SAT Trend Level –1 to 1 ^F/min SAT_TLC –0.2
Cool Min SAT Upper Level 35.0 to 65.0 °F SATMIN_H
56 (sizes 04-06)
53 (sizes 07-12)
56 (sizes 14-26)
Cool Min SAT Lower Level 35.0 to 65.0 °F SATMIN_L
46 (sizes 04-06)
42 (sizes 07-12)
46 (sizes 14-26)
Cooling Fan-off Delay 0 to 600 sec COOL_FOD 75
Circuit A Lockout Temp –20 to 75 °F OATLCMPA
0: no Economizer FIOP
40: Economizer FIOP
Low Ambient Temperature 0-80 °F LA_TEMP 66
Low Cool Lockout Temp –20 to 60 °F LCLOCKSP
10 (sizes 04-06)
30 (sizes 07-12)
40 (sizes 14-26)
Medium Cool Lockout Temp 20 to 60 °F MCLOCKSP
20 (sizes 07-12)
30 (sizes 14-26)
Humidimizer Equipped Yes/No HUMZ_EN
No: no Humidi-Mizer FIOP
Yes: Humidi-Mizer FIOP
Humidimizer Lockout Temp –20 to 75 °F OATLHUMZ
Space RH Deadband 0 % SPRH_DB
Low Refrig Charge Level 0 to 150 psi LOCHARGE 50
Low Charge Disable Temp –40 to 50 °F LOCH_LOT 10
CirA High Pressure Limit 400 to 700 psig HIPLIM_A 600
Low Discharge Level 5 to 20 °F SDTLEV 0
Minimum Pressure Ratio 0 to 5 MINPSI_R 1.35
Suction OK Temperature 10 to 50 °F SSTOK 18
Low Suction Level 1 Temp 10 to 50 °F SSTLEV1 20
Low Suction Level 2 Temp 5 to 50 °F SSTLEV2 15
Low Suction Level 3 Temp 0 to 50 °F SSTLEV3 10
Delay On Low SST Check 0 to 300 sec SSTCKDLY 0
Comp Level 2 Diag Delay 1 to 99 sec CDDTLEV2
15 (sizes 04-12)
40 (sizes 14-26)
Diag Comp Unexpected Off Enable/Disable CD_UEOFF Enable
Circuit Stuck On Diag. Enable/Disable DCKTOFF Enable
Min Discharge Change 0 to 99 psi MDP_DISA
11 (sizes 04-12)
17 sizes 14-26)
Min Suction Change 0 to 99 psi MDP_SUCA
4 (sizes 04-06)
6.5 (size 07)
8 (size 08)
7 (sizes 09-12)
14 (sizes 14-26)
CirA P.Ratio off change 1 to 1 OFFPR_A
–0.2 (sizes 04-07, 09-14)
–0.3 (sizes 08, 17-26)
Compressor Framework 0 to 2 SYSVTYPE
0 (sizes 07-26)
1 (sizes 04-06)
0 = 2 Compressors
1 = Compressor + Loader
2 = Compressor Only
Comp A1 Shutdown First Yes/No SDWN_A1
Yes (sizes 07-26)
No (sizes 04-06)
Compressor A2 Shutdown Yes/No SDWN_A2 No
Comp Loader Shutdown 1st Yes/No SDWN_ALD
No (sizes 07-26)
Yes (sizes 04-06)
ODF_CFG
Number of ODF Outputs 0 to 3 NUM_ODF
1 (sizes 04-06)
2 (sizes 07,17, or 20)
3 (sizes 08-14, 24-26)
ODF High Cool Speed 0 to 1200 rpm ODFHCSPD
1000 (size 04)
1075 (sizes 05-06)
550 (sizes 07-12)
700 (sizes 14-17, 26)
Table U — SERVICE CONFIGURATION TABLES (cont)
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT