153
HEATCFG
Type of Heat Installed
0=Electric
1=Gas
HEATTYPE
0 (50 series)
1 (48 series)
Number of Heating Stages 0 to 2 NUMHSTGS
1 (50 Series, sizes 04-06 low or
medium heat)
2 (all except below):
0 (50 series without FIOP heat),
1 (50 series, sizes 07-14 and
low heat),
1 (50 series, sizes 07-12 and
medium heat)
Heat Minimum On Time 60 to 600 sec H_MINON 120
Heat Minimum Off Time 60 to 600 sec H_MINOFF 120
Heat Stage Increase Time 120 to 999 sec HSTAGINC 450
Heating SAT Trend Level –1 to 1 ^F/min ^F/min 0.2
Heat Max SAT Lower Level 85 to 200 °F SATMAX_L 140
Heat Max SAT Upper Level 85 to 200 °F SATMAX_H 160
Heating Fan-off Delay 10 to 600 sec HEAT_FOD
30 (50 series)
45 (48 series)
Heating Lockout Temp 40 to 125 °F OATLHEAT 75
SAT Heat Mode Sensing Enable/Disable SAT_HEAT Disable
No IGC IFO Input Timeout 0 to 60 min NO_IGCTM 5
Pre-Heat HX without IDF? Enable/Disable PREHT_HX Disable
Pre-Heat Fan On Delay 0 to 120 sec PREHT_TM 30
Supply Air Tempering Enable Yes/No SATEMPEN
SA Tempering Setpoint xx °F SATEMPSP
Max OAT for SA Tempering 0 °F OATSTEMP
ECON_CFG
Economizer Installed? Yes/No ECONO
No: no FIOP
Yes: FIOP
Econ Max Damper Position 0 to 100 % DAMPMAX 100
Economizer Travel Time 5 to 300 sec ECONOTRV 150
IDF Maximum Fan Speed 80 to 100 % SPEEDMAX
Econ Min at Max Fan Speed 0 to 100 % MINP_MAX 30
Min Pos - User Speed 1 0 to 100 % MP_USPD1 0
Min Pos - User Pos 1 0 to 100 % MP_UPOS1 0
Min Pos - User Speed 2 0 to 100 % MP_USPD2 0
Min Pos - User Pos 2 0 to 100 % MP_UPOS2 0
Min Pos - User Speed 3 0 to 100 % MP_USPD3 0
Min Pos - User Pos 3 0 to 100 % MP_UPOS3 0
Low Free Cool SAT Setpnt 40 to 80 °F LCSASP 65
High Free Cool SAT Setpnt 40 to 80 °F HCSASP 55
Free Cooling Max OAT 0 to 90 °F MAXFREET 65
Free Cooling Min Temp –30 to 70 °F MINFREET 0
Diff. Dry Bulb Control Enable/Disable DIFFBULB Disable
Diff. Dry Bulb Deadband 0 to 20 °F OATRATDB 3
Max Enthalpy OA Limit 1 to 99 Btu/lb FREEMAXE 28
Diff. Enthalpy Control Enable/Disable DIFFENTH Disable
Enthalpy Cross Deadband 0 to 20 Btu/lb OAERAEDB 2
ECONO PID - KP 0.00 to 99.90 ECONO_P 2.5
ECONO PID - KI 0.00 to 99.90 ECONO_I 0.12
ECONO PID - KD 0.00 to 99.90 ECONO_D 1
ECONO PID - RATE 10 to 180 sec ECONO_DT 15
When to Unocc Free Cool? 0 to 2 UFC_CFG 1=PreOcc
0 =Disabled
1 = Pre-Occupancy
2 = Unoccupied
UFC PreOcc Time 1 to 999 min UFCTIME 120
Unocc Free Cool Low Temp –30 to 70 °F OATLUFC 50
IDF Maximum Fan Speed 80 to 100 % SPEEDMAX
PE Stage 1 at Max Speed 0 to 100 % PE1_PMAX 40
Table U — SERVICE CONFIGURATION TABLES (cont)
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES