ECON_CFG
(cont)
PE1 Relay Channel
0=NONE,
1=MBB RLY11,
2=MBB RLY06
PE1_CHAN
0: no FIOP
2: FIOP
PE Turn Off Deadband 0 to 100 % PE_OFFDB 5
PE2 Relay Channel
0=NONE,
1=MBB RLY11,
2=MBB RLY06
PE2_CHAN 0=None
PE Stage 2 at Max Speed 0 to 100 % PE2_PMAX 75
T24 Heat/Cool End Delay 0 to 60 min T24CHDLY 25
T24Econ Min Move for SAT 10 to 20 % T24ECSTS 10
Damper SAT Deadband 0 to 20 °F T24SATDB 12
T24 Min Diff in RAT-OAT 5 to 20 °F T24RATDF 15
T24 Test Minimum Pos 0 to 100 % T24TSTMN 15
T24 Test Maximum Pos 0 to 100 % T24TSTMX 85
IAQ_CFG
Analog Input IAQ Control 0 to 3 IAQANCFG
0: no FIOP
1: FIOP
0 =No IAQ
1 =DCV
2 = IAQ Override
3 =MINPOS Control
IAQ Position at Max Fan 0 to 100 % IAQMINP 10
AQ Differential Low 0 to 5000 ppm DAQ_LOW 100
AQ Differential High 0 to 5000 ppm DAQ_HIGH 700
IAQ Preoccupancy Purge Yes/No IAQPURGE Yes
IAQ Purge Pos at Max IDF 0 to 100 % IAQPMAX 40
Preocc Purge Lockout OAT 0 to 70 °F IAQP_LA 50
Preocc Purge Duration 5 to 120 min IAQPTIME 15
IAQ Sensor Value at 4mA 0 to 5000 ppm IAQ_4MA 0
IAQ Sensor Value at 20mA 0 to 5000 ppm IAQ_20MA 2000
OAQ Sensor Value at 4mA 0 to 5000 ppm OAQ_4MA 0
OAQ Sensor Value at 20mA 0 to 5000 ppm OAQ_20MA 2000
IAQ Override Sw Channel 0 to 6 IAQOCHAN
IAQ Override Switch Type Yes/No IAQOSCFG
ALM_CFG
ALM Relay Assigned Chan 0 to 2 ALM_CHAN 1=MBB RLY11
0 =None
1 =MBB RLY11
2 =MBB RLY06
Thermostat Alerts Yes/No TSTAT_AL Yes
Hardware Failures Alerts Yes/No HW_AL Yes
SAT/RAT Sensor Alerts Yes/No SATRATAL Yes
OAT Thermistor Alerts Yes/No OATRL_AL Yes
Space Sensors Alerts Yes/No SPACE_AL Yes
Transducer Sensor Alerts Yes/No TRANS_AL Yes
RH Sensor Failure Alert Yes/No RHS_AL Yes
Air Quality CO
2
Alerts Yes/No CO2S_AL Yes
OACFM Alarm Relay Yes/No OACFM_AL
Economizer Alerts Yes/No ECON_AL Yes
Dirty Filter Alerts Yes/No FILT_AL Yes
General Status Alerts Yes/No GENS_AL Yes
Refrig Circuit Alerts Yes/No CKT_AL Yes
Compressor Alerts Yes/No COMP_AL Yes
Heating Failure Alerts Yes/No HEAT_AL Yes
Indoor Fan Alerts Yes/No FAN_AL Yes
Relay on Active IOBA Yes/No IOBFA_AL
Relay on Active Faults Yes/No FAULT_AL Yes
ZSENSCFG
Zone Sensor 1 Address 0 to 255 ZSADDR1 255
Zone Sensor 2 Address 0 to 255 ZSADDR2 255
Zone Sensor 3 Address 0 to 255 ZSADDR3 255
Zone Sensor 4 Address 0 to 255 ZSADDR4 255
Zone Sensor 5 Address 0 to 255 ZSADDR5 255
Table U — SERVICE CONFIGURATION TABLES (cont)
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES