ZSENSCFG
(cont)
ZS Force Unoccup Enable No ZSFUNEN No
ZS Force Unocc Wt Delay No ZSFUNWT No
Zone Sensor Poll Rate 1 to 100 sec ZSPOLLRT 5
ZS TLO Cont Enable No ZSTLOEN No
ZS TLO Set During Occ No ZSTLSOC No
Zone Sensor UI Mode 1=Dual Offsets ZSUIM 1=Dual Offsets
Zone Sensor Unit 0=degrees F ZSUNIT 0=degrees F
TOUCHCFG
System Touch Device Inst 0 to 4194303 DEVST
System Touch Poll Rate 10 to 60 sec POLLST
System Touch AI for SPT 0 to 9999 AISTSPT
System Touch AI for SPRH 0 to 9999 AISTSPRH
TRIM
OAT Sensor Trim Offset –10 to 10 °F OAT_TRIM 0
RAT Sensor Trim Offset –30 to 30 °F RAT_TRIM 0
FST Sensor Trim Offset –10 to 10 °F FST_TRIM 0
SPT Sensor Trim Offset –30 to 30 °F SPT_TRIM 0
SPTO Sensor Offset Trim –1 to 1 °F SPTOTRIM 0
SPRH Sensor Trim Offset –15 to 15 % SPRHTRIM
IAQ Sensor Trim Offset –200 to 200 ppm IAQ_TRIM 0
OAQ Sensor Trim Offset –200 to 200 ppm OAQ_TRIM 0
OARH Sensor Trim Offset –15 to 15 % OARHTRIM 0
RARH Sensor Trim Offset –15 to 15 % RARHTRIM 0
Cir.A SSP Sensor Trim –50 to 50 psig SSPATRIM 0
Cir.A SDP Sensor Trim –50 to 50 psig SDPATRIM 0
Econ Fdback Trim Offset 15 to 15 % EC1DTRIM 0
OACFM Sensor Trim Offset –10 to 10 cfm OCFMTRIM 0
DISPLAY
Metric Display Yes/No DISPUNIT No
Display Language Select
0=English,
1=Spanish,
2=French,
3=Portuguese
LANGUAGE 0=English
LCD Contrast Adjustment 1 to 10 LCD_CONT 5
User Password Protection Enable/Disable PASS_EBL Enable
User Password 0 to 9999 PASSWORD 1111
Table U — SERVICE CONFIGURATION TABLES (cont)
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES