Space Temperature Sensor READ ONLY °F spt_loc AV:297 –40 to 245 SPT_LOC
SPRH Assigned Channel R/W sprhchan AV:372 0 to 3 SPRHCHAN
SPRH Sensor Value @ 20mA R/W % sprh_20ma AV:373 0.6 to 1 SPRH20MA
SPRH Sensor Value at 4mA R/W % sprh_4ma AV:375 0 to 0.5 SPRH_4MA
SPT Offset Range (+/-) R/W °F spto_rng AV:298 0 to 5 SPTO_RNG
SPT Offset Total diff READ ONLY °F delta sptodiff AV:6020 0 to 20 SPTODIFF
Std Barometric Pressure R/W IN_HG_OF_KPAG std_barp AV:303 10 to 35 STD_BARP
Supply Air Temp Trend READ ONLY sattrend AV:342 –285 to 285 SATTREND
Supply Air Temperature READ ONLY °F sa_temp AV:1008 -40 to 245 SAT
System Demand READ ONLY sys_demand AV:37 0 to 255 SYS_DMD
System Demand Alert R/W sys_dmd_alert AV:227 0 to 65535 SYSDMDAT
System ODF speed test R/W RPM s_odfspd AV:123 0 to 1200 S_ODFSPD
System Touch AI for SPRH R/W aistsprh AV:8027 0 to 9999 AISTSPRH
System Touch AI for SPT R/W aistspt AV:8026 0 to 9999 AISTSPT
System Touch Device Inst R/W devst AV:8024 0 to 4194303 DEVST
System Touch Poll Rate R/W pollst AV:8025 10 to 60 POLLST
System Touch RH Value R/W % strh_net AV:8022 0 to 1 STRH_NET
System Touch Temp Value R/W °F stst_net AV:8023 –40 to 245 STST_NET
T24 Heat/Cool End Delay R/W min t24chdly AV:305 0 to 60 T24CHDLY
T24 Min Diff in RAT-OAT R/W °F t24ratdf AV:307 5 to 20 T24RATDF
T24 Test Maximum Pos R/W % t24tstmx AV:310 0.0f to 1.0f T24TSTMX
T24 Test Minimum Pos R/W % t24tstmn AV:309 0.0f to 1.0f T24TSTMN
T24Econ Min Move for SAT R/W % t24ecsts AV:306 0.1 to 0.2 T24ECSTS
Timed Override Duration R/W hrs otl_cfg AV:179 0 to 4 OTL_CFG
Timed Override Hours R/W min ovr_ext AV:180 0 to 240 OVR_EXT
TLO cancel R/W sec tlocan AV:6029 0 to 10 TLOCAN
TLO limit R/W sec tlolim AV:6027 0 to 14400 TLOLIM
TLO Time Remaining READ ONLY sec tlorem AV:6028 0 to 14400 TLOREM
UFC PreOcc Time R/W min ufctime AV:105 1 to 999 UFCTIME
Unit Full Load Run Hours READ ONLY hrs hour_full_ld AV:52 0 to 999999 HR_FLOAD
Unit Full Load Starts READ ONLY st_fload AV:140 0 to 999999 ST_FLOAD
Unit Startup Delay R/W sec startdly AV:153 10 to 600 STARTDLY
Unocc Free Cool Low Temp R/W °F oatlufc AV:287 –30.0f to 70.0f OATLUFC
Unoccupied Cool Setpoint R/W °F ucsp AV:8 65 to 95 UCSP
Unoccupied Heat Setpoint R/W °F uhsp AV:178 40 to 80 UHSP
Unoccupied Setpoint Gap R/W udb AV:6004 0 to 55 UDB
Unoccupied SPRH Setpoint READ ONLY % sprh_usp AV:461 0.10 to 1 SPRH_USP
UnoccupiedZone Setpoint R/W °F usp AV:6005 40 to 95 USP
User Min Pos Pnt 1 Valid READ ONLY mp_upt1 AV:332 0 to 1 MP_UPT1
User Min Pos Pnt 2 Valid READ ONLY mp_upt2 AV:333 0 to 1 MP_UPT2
User Min Pos Pnt 3 Valid READ ONLY mp_upt3 AV:214 0 to 1 MP_UPT3
User Password R/W password AV:181 0 to 9999 PASSWORD
Value of Prime variable READ ONLY prime_v AV:39 –40 to 245 PRIME_V
Vent IDF Resets Count READ ONLY rs_ventf AV:117 0 to 65535 RS_VENTF
Vent IDF Run Hours READ ONLY hrs hour_vent_fan AV:64 0 to 999999 HR_VENTF
Ventilation Fan Starts READ ONLY st_ventf AV:152 0 to 999999 ST_VENTF
Ventilation Only IDF Spd R/W % idf_vent_speed AV:9 0 to 1 FSPDVENT
Zone Sensor 1 Address R/W zsaddr1 AV:8034 0x00 to 0xFF ZSADDR1
Zone Sensor 2 Address
R/W zsaddr2 AV:8035 0x00 to 0xFF ZSADDR2
Zone sensor 3 address R/W zsaddr3 AV:8036 0x00 to 0xFF ZSADDR3
Zone sensor 4 address R/W zsaddr4 AV:8037 0x00 to 0xFF ZSADDR4
Zone sensor 5 address R/W zsaddr5 AV:8038 0x00 to 0xFF ZSADDR5
ZS Zone Temp R/W °F ZSZoneTemp AV:1905 –40 to 245 ZSZT
Table Y — BACnet* AV Points List (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACNET
OBJECT NAME
BACNET
ID
VALUE
RANGE
CCN POINT
EQUIVALENT
APPENDIX E — BACNET POINTS LIST