170
Ok to fan based dehum READ ONLY oktofbd BV:420 0 to 1 OKTOFBD
Ok to Dehumidify? READ ONLY oktodhum BV:422 0 to 1 OKTODHUM
Ok to Preoccupancy Purge READ ONLY okpreocc BV:35 0 to 1 OKPREOCC
OK to Run Heat READ ONLY oktoheat BV:36 0 to 1 OKTOHEAT
OK to SupplyAirTempering READ ONLY oktotemp BV:415 0 to 1 OKTOTEMP
Ok to Unocc Free Cool? READ ONLY oktoufc BV:37 0 to 1 OKTOUFC
Ok to use compressors? READ ONLY okmechcl BV:302 0 to 1 OKMECHCL
OK to Use Free Cooling? READ ONLY ok_free_cl BV:65 0 to 1 OKFREECL
Ok to use humidimizer READ ONLY oktohumz BV:421 0 to 1 OKTOHUMZ
Percent Enable/Disable R/W perc_bac BV:303 0 to 1 PERC_BAC
Power Exhaust 1 Relay R/W pe1 BV:15 0 to 1 PE1
Power Exhaust 1 Test R/W s_pe_1 BV:82 0 to 1 S_PE_1
Power Exhaust 2 Relay R/W pe2 BV:66 0 to 1 PE2
Power Exhaust 2 Test R/W s_pe_2 BV:83 0 to 1 S_PE_2
RARH Open Circuit Alert R/W a_opnrrh BV:199 0 to 1
RARH Sensor Error R/W rarh_err BV:67 0 to 1 RARH_ERR
RARH Short Circuit Alert R/W a_shtrrh BV:210 0 to 1
RAT Open Circuit Alert R/W a_opnrat BV:198 0 to 1
RAT out of Range Alert R/W a_badrat BV:187 0 to 1
RAT out of Range Alert R/W a_badsat BV:188 0 to 1
RAT Sensor Error R/W rat_err BV:68 0 to 1 RAT_ERR
RAT Short Circuit Alert R/W a_shtrat BV:209 0 to 1
Refrig Circuit Alerts R/W circuit_alarm BV:313 0 to 1 CKT_AL
Reheat Dischg Valve CirA R/W rdv_a BV:7012 0 to 1 RDV_A
Reheat Liq Valv Rly Test R/W s_rlv_a BV:455 0 to 1 S_RLV_A
Reheat Liquid Valve CirA R/W rlv_a BV:7051 0 to 1 RLV_A
Remote Occupancy Switch R/W remocc BV:29 0 to 1 REMOCC
Remote shutdown fault R/W f_remoff BV:272 0 to 1
Remote Shutdown Switch R/W rem_shut BV:9001 0 to 1 REMSHUT
Reset All Current Alarms R/W alarm_reset BV:33 0 to 1 ALRESET
Reset Filter Timer R/W reset_filter_timer BV:109 0 to 1 RESETFLT
RH sensor failure Alert R/W rhs_al BV:308 0 to 1 RHS_AL
Rht Dischg Valve Rly Tst R/W s_rdv_a BV:282 0 to 1 S_RDV_A
Rollout without Heating R/W f_ronoht BV:235 0 to 1
RUN AUTO COOLING TEST R/W autocool BV:160 0 to 1 AUTOCOOL
RUN AUTO HEATING TEST R/W autoheat BV:161 0 to 1 AUTOHEAT
RUN AUTO SYSTEM TEST R/W autosys BV:162 0 to 1 AUTOSYS
Run away heat fault R/W f_hstuck BV:266 0 to 1
SAT Sensor Error R/W sat_err BV:84 0 to 1 SAT_ERR
SAT/RAT Sensor Alerts R/W sa_ra_alarm BV:311 0 to 1 SATRATAL
SDPA Sensor Error R/W sdpa_err BV:63 0 to 1 SDPA_ERR
Shut Down on IDF Failure R/W sfan_fail_alarm BV:7008 0 to 1 FATALFAN
Shutdown A1 First R/W sdwn_a1 BV:449 0 to 1 SDWN_A1
Shutdown A2 First R/W sdwn_a2 BV:450 0 to 1 SDWN_A2
Shutdown Loader First R/W sdwn_ald BV:451 0 to 1 SDWN_ALD
Smoke Purge Input R/W purge BV:80 0 to 1 PURGE
Space Sensors Alerts R/W space_alarm BV:103 0 to 1 SPACE_AL
SPRH Open Circuit Alert R/W a_opnsrh BV:274 0 to 1
SPRH Short Circuit Alert R/W a_shtsrh BV:275 0 to 1
SPT Open Circuit Alert R/W a_opnspt BV:201 0 to 1
SPT Sensor Error
R/W space_err BV:7001 0 to 1 SPT_ERR
SPT Short Circuit Alert R/W a_shtspt BV:212 0 to 1
SPTO Sensor Error R/W stpt_err BV:7002 0 to 1 SPTO_ERR
SPToutofRangeAlert R/W a_badspt BV:190 0 to 1
SSPA Sensor Error R/W sspa_err BV:89 0 to 1 SSPA_ERR
Start Config Restore READ ONLY ddrstre BV:130 0 to 1 DDRSTRE
Supply Air Temper Enable R/W sup_air_temp_en BV:410 0 to 1 SATEMPEN
System Demand Alarm R/W sys_dmd_alarm BV:26 0 to 1 SYSDMDAL
Temp Compensate Start On READ ONLY tcs_Act BV:133 0 to 1 TCS_ACT
Thermostat Alerts R/W tstat_al BV:104 0 to 1 TSTAT_AL
Thermostat G Input R/W g_input BV:1021 0 to 1 G
Table Z — BACnet* BV Points List (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACNET
OBJECT NAME
BACNET
ID
VALUE
RANGE
CCN POINT
EQUIVALENT
APPENDIX E — BACNET POINTS LIST