169
IAQ Short Circuit Alert R/W a_shtiaq BV:205 0 to 1
IDF Manual Transition R/W s_idftrn BV:78 0 to 1 S_IDFTRN
IDF Operation Errors? READ ONLY idf_bad BV:52 0 to 1 IDFBAD
IDF Speed Override Flag READ ONLY sfan_hand_alarm BV:7009 0 to 1 FAN_OVRD
IDF Speed Reduction On READ ONLY fanred10 BV:7 0 to 1 FANRED10
IDF VFD Com Failure R/W f_vfdcf BV:254 0 to 1
IDF VFD Earth fault R/W f_vfdef BV:255 0 to 1
IDF VFD Hand Alert R/W a_vfdhnd BV:227 0 to 1
IDF VFD Internal V Low R/W f_vfdivl BV:256 0 to 1
IDF VFD Low V Error R/W f_vfdlve BV:257 0 to 1
IDF VFD Main Power Fail R/W f_vfdmpf BV:258 0 to 1
IDF VFD Motor In Reverse R/W vfd1mdir BV:102 0 to 1 VFD1MDIR
IDF VFD Motor Over Temp R/W f_vfdmot BV:418 0 to 1
IDF VFD Over Current R/W f_vfdov BV:261 0 to 1
IDF VFD Over Temperature R/W f_vfdot BV:249 0 to 1
IDF VFD Over Voltage R/W f_vfdoc BV:259 0 to 1
IDF VFD Overload R/W f_vfdol BV:260 0 to 1
IDF VFD Phase U Loss R/W f_vfdpul BV:250 0 to 1
IDF VFD Phase V Loss R/W f_vfdpwl BV:252 0 to 1
IDF VFD Phase W Loss R/W f_vfdpvl BV:251 0 to 1
IDF VFD Short Circuit R/W f_vfdsc BV:262 0 to 1
IDF VFD Undervoltage R/W f_vfduv BV:263 0 to 1
IDF VFD Unexpected Fault R/W f_vfdune BV:253 0 to 1
IDF VFD Warning Alert R/W a_vfdwar BV:228 0 to 1
IGC Fan On Request (IFO) READ ONLY igc_ifo BV:13 0 to 1 IGC_IFO
Ignition Failure Alert R/W a_noign BV:222 0 to 1
In Pre-Occupancy Purge? READ ONLY preoccon BV:38 0 to 1 PREOCCON
Indoor Fan Alerts R/W idf_alarm BV:45 0 to 1 FAN_AL
Is IAQ Override Active? READ ONLY iaq_ovrd BV:164 0 to 1 IAQ_OVRD
Linkage Active READ ONLY link_active BV:58 0 to 1 LNK_ACT
Liq Diverter Val Rly Tst R/W s_ldv_a BV:281 0 to 1 S_LDV_A
Liquid Diverter Val CirA R/W ldv_a BV:7011 0 to 1 LDV_A
Local Sched Occ Request R/W loc_occ BV:95 0 to 1 LOC_OCC
Loss of comms with SIOB READ ONLY a_sioblc BV:9003 0 to 1
Low cooling locked out READ ONLY lc_lock BV:317 0 to 1 LC_LOCK
Make Config Backup File R/W ddbckup BV:129 0 to 1 DDBCKUP
MBB 24VDC Alert R/W a_mbb24d BV:247 0 to 1
MBB 5VDC Alert R/W a_mbb5dc BV:248 0 to 1
MBB EEPROM failure fault R/W f_mbbeep BV:267 0 to 1
MBB Fuse 2 Fault R/W f_mbbf2 BV:268 0 to 1
MBB Fuse 3 Fault R/W f_mbbf3 BV:269 0 to 1
MBB low voltage Fault R/W f_mbblov BV:270 0 to 1
MBB Ref Volt Fail Fault R/W f_mbbref BV:271 0 to 1
MBB RNET Voltage Alert R/W a_mbb12d BV:246 0 to 1
MBB zero crossing alert R/W a_mbb0x BV:245 0 to 1
Mechanical Cool active? READ ONLY mechcool BV:301 0 to 1 MECHCOOL
Medium Cooling lockout READ ONLY mc_lock BV:318 0 to 1 MC_LOCK
OACFM Alarm Relay R/W oacfm_rel_alarm BV:371 0 to 1 OACFM_AL
OACFM Open Circuit Alert R/W a_opnoac BV:276 0 to 1
OACFM ShortCircuit Alert R/W a_shtoac BV:277 0 to 1
OAQ Open Circuit Alert
R/W a_opnoaq BV:195 0 to 1
OAQ Short Circuit Alert R/W a_shtoaq BV:206 0 to 1
OARH Open Circuit Alert R/W a_opnorh BV:197 0 to 1
OARH Sensor Error R/W oarh_err BV:60 0 to 1 OARH_ERR
OARH Short Circuit Alert R/W a_shtorh BV:208 0 to 1
OAT Open Circuit Alert R/W a_opnoat BV:196 0 to 1
OAT out of Range Alert R/W a_badoat BV:186 0 to 1
OAT Sensor Error R/W oat_error BV:314 0 to 1 OAT_ERR
OAT Short Circuit Alert R/W a_shtoat BV:207 0 to 1
OAT Thermistor Alerts R/W oat_rel_alarm BV:61 0 to 1 OATRL_AL
ODF Manual Transition R/W s_odftrn BV:81 0 to 1 S_ODFTRN
Table Z — BACnet* BV Points List (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACNET
OBJECT NAME
BACNET
ID
VALUE
RANGE
CCN POINT
EQUIVALENT
APPENDIX E — BACNET POINTS LIST