168
Currently Occupied R/W occ_status BV:2008 0 to 1 OCCUPIED
Damper fdbk out of range R/W a_badec1 BV:184 0 to 1
Damper fdbk Short Alert R/W a_shtec1 BV:203 0 to 1
Damper Not Mod Alert R/W a_dnm BV:215 0 to 1
Damper Stuck Closed Alrt R/W a_dnm_sc BV:216 0 to 1
Damper Stuck Open Alert R/W a_dnm_so BV:217 0 to 1
DD IDF High Speed Relay READ ONLY fspdhrly BV:448 0 to 1 FSPDHRLY
DD IDF Low Speed Relay READ ONLY fspdlrly BV:446 0 to 1 FSPDLRLY
DD IDF Med. Speed Relay READ ONLY fspdmrly BV:447 0 to 1 FSPDMRLY
Diff. Dry Bulb Control R/W dif_db_ena BV:41 0 to 1 DIFFBULB
Diff. Enthalpy Control R/W dif_enth_ena BV:42 0 to 1 DIFFENTH
dirty filter alert R/W a_dfilt BV:214 0 to 1
Dirty Filter Alerts R/W filter_alarm BV:7017 0 to 1 FILT_AL
Dmpr fdbk Open Cir Alert R/W a_opnec1 BV:192 0 to 1
Dry Bulb Lockout R/W db_lock_out BV:40 0 to 1 DBLOCK
DST allowed? R/W dst_cfg BV:93 0 to 1 DST_CFG
DST currently active READ ONLY dst_actv BV:92 0 to 1 DST_ACTV
Econ Damper Operational READ ONLY damp_good BV:39 0 to 1 DAMPGOOD
Econo Actual Position R/W dmpr_err BV:21 0 to 1 DAMP_ERR
Economizer Alerts R/W econ_alarm BV:43 0 to 1 ECON_AL
Economizer Cooling R/W a_t24ewc BV:226 0 to 1
Economizer Installed? R/W econo_cfg BV:131 0 to 1 ECONO
Economizer Not Cooling R/W a_t24enc BV:224 0 to 1
Enthalpy Lockout R/W enth_lock_out BV:44 0 to 1 ENTHLOCK
Excess Outside Air Alert R/W a_t24eoa BV:225 0 to 1
Fan Off When Cmded On R/W f_idfoff BV:230 0 to 1
Fan On When Cmded Off R/W f_idfon BV:231 0 to 1
Fan On When Occupied R/W occupied_fan BV:46 0 to 1 FANON_OC
fan status warning alert R/W a_idfwar BV:219 0 to 1
fbdh sat locked out READ ONLY fbdsatlo BV:439 0 to 1 FBDSATLO
FBDH SST locked out READ ONLY fbdsstlo BV:440 0 to 1 FBDSSTLO
Filter Status Switch R/W flt_status BV:1016 0 to 1 FILTSTAT
Fire shutdown fault R/W f_fire BV:242 0 to 1
Fire Shutdown Switch R/W firedown BV:112 0 to 1 FIREDOWN
FSPDHRLY IDF Test R/W s_fshrly BV:464 0 to 1 S_FSHRLY
FSPDLRLY IDF Test R/W s_fslrly BV:462 0 to 1 S_FSLRLY
FSPDMRLY IDF Test R/W s_fsmrly BV:463 0 to 1 S_FSMRLY
FST Open Circuit Alert R/W a_opnfst BV:193 0 to 1
FST out of Range Alert R/W a_badfst BV:185 0 to 1
FST Sensor Error R/W fst_error BV:49 0 to 1 FST_ERR
FST Short Circuit Alert R/W a_shtfst BV:204 0 to 1
General Status alert R/W a_gensw BV:244 0 to 1
General Status Alerts R/W gens_al BV:309 0 to 1 GENS_AL
General Status fault R/W f_gensw BV:265 0 to 1
General Status Switch R/W gen_status BV:50 0 to 1 GENSTAT
Hardware Failures Alerts R/W hw_al BV:305 0 to 1 HW_AL
Heat Stage 1 Available READ ONLY ht1_aval BV:16 0 to 1 HT1_AVAL
Heat Stage 1 Relay READ ONLY hs1 BV:10 0 to 1 HEAT_1
Heat Stage 2 Available READ ONLY ht2_aval BV:17 0 to 1 HT2_AVAL
Heat Stage 2 Relay READ ONLY hs2 BV:11 0 to 1 HEAT_2
HeatDemandLimiting
R/W heatdmdLimit BV:370 0 to 1 HDMLMOFF
Heating Failure Alerts R/W heat_al BV:306 0 to 1 HEAT_AL
Heating Stage 1 Test R/W s_heat1 BV:76 0 to 1 S_HEAT1
Heating Stage 2 Test R/W s_heat2 BV:77 0 to 1 S_HEAT2
Humidimizer Status R/W humz_en BV:7010 0 to 1 HUMZ_EN
humidity ctrl is active READ ONLY humctrla BV:423 0 to 1
IAQ Open Circuit Alert R/W a_opniaq BV:194 0 to 1
IAQ override enable R/W iaq_override_en BV:445 0 to 1 IAQOVREN
IAQ override sw state R/W iaqoverride_switch BV:7030 0 to 1 IAQ_OVRS
IAQ Preoccupancy Purge R/W iaqpurge BV:20 0 to 1 IAQPURGE
IAQ Sensor Error R/W iaq_err BV:51 0 to 1 IAQ_ERR
Table Z — BACnet* BV Points List (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACNET
OBJECT NAME
BACNET
ID
VALUE
RANGE
CCN POINT
EQUIVALENT
APPENDIX E — BACNET POINTS LIST