UNIT CONFIGURATIONS (cont)
TEST MODE TIMEOUT Test inactivity time out
0=Disabled,
1=30 minutes,
2=1 hour,
3=2 hours,
4=4 hours,
5=8 hours,
6=12 hours
4=4 hours TEST_ITO
CCH MAX TEMP CCH Max Temperature 40 to 90 °F 65 CCHMAXT
STD BARO PRESSURE Std Barometric Pressure 13.00 to 35.00 in. Hg 29.92 STD_BARP
LINK STAGEUP TIME Linkage Stage inc. time 60 to 600 sec 180 LSTAGINC
UNIT’S MAX SAT Unit’s Maximum SAT 130 to 210 °F 200 UMAX_SAT
AUTO SAT FAULTS? Auto Clr SAT Limit Fault Yes/No No SATLACLR
ADAPTIVE TCS? Adaptive Temp Comp Start Enable/Disable Enable TCS_CFG
USER TCS BIASTIME User TCS Start bias time 0 to 180 min 0 TCSUBIAS
SWITCH INPUTS CONFIGS DI Config Menu
FIRE SHUTDOWN SW Fire Shutdown Switch
0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
2: no FIOP
0: FIOP
FIRE_CFG
HUMSTAT CHANNEL Humidistat Status Channel
0=None,
1=MBB DI12,
2=MBB DI13.
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB Di01
0=for all except
Humidimizer
6=Humidimizer
Units
HUMDCHAN
HUMSTAT SW TYPE Humidistat Switch Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN HUMD_CFG
FILTER SW CHANNEL Filter Status Sw Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None FILTCHAN
FILTER SW TYPE Filter Status Switch Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN FILT_CFG
REMOTE OCC CHAN Remote Occupancy Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None
RMOCCHA
N
REMOTE OCC TYPE Remote Occupancy Sw Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN RMOC_CFG
REM.SHUTDOWN CHAN Remote Shutdown Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ROFFCHAN
REM.SHUTDOWN SW T Remote Shutdown Sw Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN ROFF_CFG
REM.SHUTDOWN TYPE Remote Shutdown ALM Type
0=Normal,
1=Emergency
0=Normal ROFFTYPE
COFS CHANNEL COFS Assigned Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None (no
FIOP)
4=MBB DI02
(FIOP)
COFSCHAN
COFS TYPE COFS Switch Type
0=NORM OPEN,
1=NORM CLSD
1=NORM CLSD COFS_CFG
GEN STATUS CHAN General Status Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None GEN_CHAN
GEN STAT SW TYPE General Status Sw Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN GENS_CFG
SHUTDOWN GEN STAT General Status shutdown? Yes/No Yes GENFATAL
Table AC — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT ENTRY
CONTROL SET POINT AND CONFIGURATION LOG