UNIT CONFIGURATIONS (cont)
ENTHALPY SW CHAN Enthalpy Sw Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ENTHCHAN
ENTHALPY SW TYPE Enthalpy Switch Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN ENTH_CFG
IAQ OVERIDE SW CH IAQ override sw channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB DI01
IAQOCHAN
IAQ OVRRD SW TYPE IAQ Override Switch Type
0=NORM OPEN,
1=NORM CLSD
IAQOSCFG
ANALOG INPUT CONFIGS
Analog Inputs Configuration
Menu
SPRH SENS CHANNEL SPRH Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
4=SIOB AI10
0=None SPRHCHAN
SPRH RH @ 4MA SPRH Sensor Value at 4mA 0 to 100 % 0 SPRH_4MA
SPRH RH @ 20MA SPRH Sensor Value at 20mA 0 to 100 % 1 SPRH20MA
IAQ SENSOR CHAN IAQ Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: no FIOP
1: FIOP
IAQ_CHAN
IAQ PPM@ 4MA IAQ Sensor Value at 4mA 0 to 5000 ppm 0 IAQ_4MA
IAQ PPM@ 20MA IAQ Sensor Value at 20mA 0 to 5000 ppm 2000 IAQ_20MA
OAQ SENSOR CHAN OAQ Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None OAQ_CHAN
OAQ PPM@ 4MA OAQ Sensor Value at 4mA 0 to 5000 ppm 0 OAQ_4MA
OAQ PPM@ 20MA OAQ Sensor Value at 20mA 0 to 5000 ppm 2000 OAQ_20MA
OARH SENSOR CHAN OARH Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: no Enthalpy
FIOP
3: Enthalpy
FIOP
OARHCHAN
OARH RH @ 4MA OARH Sensor Value at 4mA 0 to 100 % 0 OARH_4MA
OARH RH @ 20MA OARH Sensor Val. at 20mA 0 to 100 % 100 OARH20MA
RARH SENS CHANNEL RARH Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None RARHCHAN
RARH RH @ 4MA RARH Sensor Value at 4mA 0 to 100 % 0 RARH_4MA
RARH RH @ 20MA RARH Sensor Value at 20mA 0 to 100 % 100 RARH20MA
OACFM SENSOR CHAN OACFM Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
0=None OCFMCHAN
OACFM@ 4MA OACFM value at 4mA 0 to 100 CFM 0 OCFM_4MA
OACFM@ 20MA OACFM Value at 20mA 0 to 100 CFM 20 OCFM20MA
COOLING Cooling Configurations Menu
LOW COOL COMP Low Cool Compressor 1 to 2 1 LC_COMP
COMP MIN ON TIME Compressor Min On Time 180 to 600 sec 300 C_MINON
COMP MIN OFF TIME Compressor Min Off Time 120 to 600 sec 180 C_MINOFF
STRIKE CLEAR TIME Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S
COOL STAGEUP TIME Cool Stage Increase Time 120 to 999 sec 450 CSTAGINC
COOL SATTREND LEV Cooling SAT Trend Level –1.0 to 1.0 –0.2 SAT_TLC
UPPER MIN SAT Cool Min SAT Upper Level 35.0 to 65.0 °F
53 (sizes 07-12)
56 (sizes 04-06,
14-26)
SATMIN_H
LOWER MIN SAT Cool Min SAT Lower Level 35.0 to 65.0 °F
42 (sizes 07-12)
46 (sizes 04-06,
14-26)
SATMIN_L
SPRH DEADBAND Space RH Deadband 0 % 5 SPRH_DB
Table AC — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT ENTRY
CONTROL SET POINT AND CONFIGURATION LOG