178
COOLING (cont)
HUMZ LOCKOUT OAT Humidimizer Lockout Temp –20 to 75 °F 40 OATLHUMZ
HUMZ ENABLE Humidimizer Equipped Yes/No
No: no Humidi-
Mizer FIOP
Yes: Humidi-
Mizer FIOP
HUMZ_EN
COOL FANOFF DELAY Cooling Fan-off Delay 0 to 600 sec 75 COOL_FOD
FBD CONTROL TYPE Fan Based Dehum Type
0=NONE,
1=Comfort,
2=Max
0=NONE FBD_TYPE
FBD LOW SP FBDH Low Set Point –20 to 0 °F delta –2.5 FBDLO_SP
FBD SST SETPOINT FBDH Max Mode SST SP 20 to 60 °F 38 FBDSSTSP
FBD SST MIN VALUE FBDH Min SST Threshold 10 to 60 °F 32 FBDH_SST
FBD COMFORT SAT FBDH Comfort SAT SP 35 to 80 °F 46 FBDH_SAT
FBDSAT COMF DELTA FBD Comfort SAT Delta 0 to 40 °F 11 FBDSATDT
FBD MIN IDF SPEED Minimum IDF Speed 0 to 100 % 25 FBDMINSP
FBD MAX IDF SPEED FBD Fan Max 0 to 100 % 100 FBDFMAX
LOW AMBIENT
LOW AMBIENT CONFIGS
MENU
CIR.A LOCKOUT OAT Circuit A Lockout Temp –20 to 75 °F
0: no
Economizer
FIOP
40: Economizer
FIOP
OATLCMPA
LOW AMBIENT TEMP Low Ambient Temperature 0 to 80 °F 66 LA_TEMP
LOW COOL MIN OAT Low Cool lockout Temp –20 to 60 °F
10 (sizes 04-06)
30 (sizes 07-12)
40 (sizes 14-26)
LCLOCKSP
MED COOL MIN OAT Medium Cool lockout Temp –20 to 60 °F
20 (sizes 04-12)
30 (sizes 14-26)
MCLOCKSP
LA DEHUM LEV 1 Low Ambient Dehum Lev 1 40 to 125 °F 80 LAHTEMP1
LA DEHUM LEV 2 Low Ambient Dehum Lev 2 40 to 125 °F 61 LAHTEMP2
LA DEHUM LEV 3 Low Ambient Dehum Lev 3 40 to 125 °F 55 LAHTEMP3
LA DEHUM SDT SP 1 LA Dehum SDT SP Lev 1 60 to 120 °F 93 LHSDTSP1
LA DEHUM SDT SP 2 LA Dehum SDT SP Lev 2 60 to 120 °F 93 LHSDTSP2
LA DEHUM SDT SP 3 LA Dehum SDT SP Lev 3 60 to 120 °F 104 LHSDTSP3
CHARGE DIAGNOSTICS
Refrigerant Charge Diagnostic
Config Menu
LOW CHARGE LEVEL Low Refrig Charge Level 0 to 150 psi 50 LOCHARGE
NO LOW CHARGE OAT Low Charge Disable Temp –40 to 50 °F 10 LOCH_LOT
CIR.A SDP LIMIT CirA High Pressure Limit 400 to 700 psi 600 HIPLIM_A
LOW DISCHARGE LEV Low Discharge Level 0 to 20 °F 0 SDTLEV
MIN PRESS RATIO Minimum Pressure Ratio 0 to 5 1.35 MINPSI_R
LOW SUCTION DIAG.
Low Suction Diagnostic Config
Menu
LOW SUC OK TEMP Suction OK Temperature 10 to 50 °F 18 SSTOK
LOW SUC LEVEL 1 Low Suction Level 1 Temp 10 to 50 °F 20 SSTLEV1
LOW SUC LEVEL 2 Low Suction Level 2 Temp 5 to 50 °F 15 SSTLEV2
LOW SUC LEVEL 3 Low Suction Level 3 Temp 0 to 50 °F 10 SSTLEV3
LO SUC DIAG DELAY Delay On Low SST Check 0 to 300 sec 0 SSTCKDLY
COMPRESSOR
TRANSISTION
Compressor Transition
diagnostic config menu
COMP L2 DIAG DLY Comp level 2 Diag Delay 1 to 99 sec
15 (sizes 04-12)
40 (sizes 14-26)
CDDTLEV2
IAG. COMP OFF Diag Comp Unexpected Off Enable/Disable Enabled CD_UEOFF
CIR STUCK ON DIAG Circuit Stuck On Diag. Enable/Disable Enabled DCKTOFF
CIR.A MIN DIS.P Min discharge change 0 to 99 psi
11 (sizes 04-12)
17 (sizes 14-26)
MDP_DISA
CIR.A MIN SUC.P Min Suction change 0 to 99 psi
4 (sizes 04-06)
6.5 (size 07)
8 (size 08)
7 (sizes 09-12)
14 (sizes 14-26)
MDP_SUCA
OFF P.RATIO CirA P.Ratio off change –1 to 1
–0.2 (sizes 07,
09-14)
–0.3 (sizes 08,
17-26)
OFFPR_A
Table AC — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT ENTRY
CONTROL SET POINT AND CONFIGURATION LOG