ODF SETTINGS
Outdoor Fans Configurations
Menu
ODF SIGNAL QTY Number of ODF Outputs 0 to 3
1 (sizes 04-06)
2 (sizes 07,17,
or 20)
3 (sizes 08-14,
24-26)
NUM_ODF
ODF LOW COOL SPD ODF Low Cool Speed 0 to 1200 rpm
1000 (size 04)
1075 (sizes 05-
06)
550 (sizes 07-
12)
700 (sizes 14-
17, 26)
650 (sizes 20-
24)
ODFLCSPD
ODF MED COOL SPD ODF Med Cool Speed 0 to 1200 rpm
1000 (size 04)
1075 (sizes 05-
06)
700 (sizes 07,
12, or 24)
600 (size 08)
650 (size 09)
800 (sizes
14,17, or 26)
750 (size 20)
ODFMCSPD
ODF HIGH COOL SPD ODF High Cool Speed 0 to 1200 rpm
1000 (size 04)
1075 (sizes 05-
06)
950 (sizes 07 or
09)
900 (size 08)
1000 (sizes 12-
26)
ODFHCSPD
ODF MAXIMUM SPEED ODF Maximum Speed 0 to 1200 rpm
1000 (size 04)
1075 (sizes 05-
06)
950 (sizes 07 or
09)
900 (size 08)
1000 (sizes 12-
26)
ODFMAXSP
ODF MINIMUM SPEED ODF Minimum Speed 0 to 1200 rpm 160 ODFMINSP
HEATING Heating Configurations Menu
UNIT TYPE OF HEAT Type of Heat Installed
0=ELECTRIC,
1=GAS
0 (50 series)
1 (48 series)
HEATTYPE
HEATING STAGE QTY Number of Heating Stages 0 to 2
2 (all except
below);
0 (50 series
without
FIOP heat),
1 (50 Series,
sizes 04-06 low
or medium
heat),
1 (50 series,
sizes
07-14 and low
heat),
1 (50 series,
sizes 07-12 and
medium heat)
NUMHSTGS
HEAT MIN ON Heat Minimum On Time 60 to 600 sec 120 H_MINON
HEAT MIN OFF Heat Minimum Off Time 60 to 600 sec 120 H_MINOFF
HEAT STAGEUP TIME Heat Stage Increase Time 120 to 999 sec 450 HSTAGINC
HEAT SATTREND LEV Heating SAT Trend Level -1 to 1.0 ^F/min 0.2 SAT_TLH
LOWER MAX SAT Heat Max SAT Lower Level 85.0 to 200.0 °F 140 SATMAX_L
UPPER MAX SAT Heat Max SAT Upper Level 85.0 to 200.0 °F 160 SATMAX_H
HEAT FANOFF DELAY Heating Fan-off Delay 10 to 600 sec
30 (50 series)
45 (48 series)
HEAT_FOD
HEAT LOCKOUT OAT Heating Lockout Temp 40 to 125 °F 75 OATLHEAT
SAT DURING HEAT? SAT Heat Mode Sensing Enable/Disable Enable SAT_HEAT
IGC IFO TIMEOUT No IGC IFO input Timeout 0 to 60 min 5 NO_IGCTM
PREHEAT W/O IDF? Pre-Heat HX without IDF? Enable/Disable Disable PREHT_HX
PREHEAT FAN DELAY Pre-Heat Fan On Delay 0 to 120 sec 30 PREHT_TM
SA TEMPER ENABLED Supply Air Tempering Enable Yes/No Yes SATEMPEN
Table AC — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT ENTRY
CONTROL SET POINT AND CONFIGURATION LOG