180
HEATING (cont)
SA TEMPER SET PNT SA tempering Setpoint xx °F 50 SATEMPSP
TEMPER MAX OUT Max OAT for SA tempering -40 to 125 °F 48 OATSTEMP
INDOOR FAN
Indoor Fan Configurations
Menu
INDOOR FAN TYPE Indoor Fan Type
0=None,
1=VFD,
2=DIRECT DRIVE
1=VFD: all
except Direct
Drive motor
Option
2 = DIRECT
DRIVE: on 04-
06 size with
direct drive
motors
IDFTYPE
DIR.DRV IDF SPDS Number Of Fan Speeds 2 to 3 2 NUMFSPDS
OCCUPIED FAN? Fan On When Occupied Yes/No Yes FANON_OC
MAXIMUM IDF SPEED IDF Maximum Fan Speed 80 to 100 % 100 SPEEDMAX
VENT IDF SPEED Ventilation Only IDF Spd 0 to 100 %
50 (sizes 04-06)
67 (sizes 07-12)
53 (sizes 14 or
20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
FSPDVENT
HEATING IDF SPD Heating IDF Speed 20-100 % 100 FSPD_HT
FREE COOL IDF SPD Free Cooling IDF Speed 0-100 %
70 (size 04)
57 (sizes 05-06)
67 (sizes 07-12)
53 (sizes 14 or
20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
FSPD_FCL
LOW COOL IDF SPD Low Cooling IDF Speed 20-100 %
70 (size 04)
57 (sizes 05-06)
67 (sizes 07-12)
53 (sizes 14 or
20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
FSPD_LCL
MED COOL IDF SPD Med Cooling IDF Speed 20-100 %
87 (sizes 04)
71 (sizes 05)
69 (sizes 06)
67 (sizes 07-12)
79 (sizes 14)
82 (sizes 17)
62 (sizes 20)
65 (sizes 24)
72 (sizes 26)
FSPD_MCL
HIGH COOL IDF SPD High Cooling IDF Speed 20-100 % 100 FSPD_HCL
SHUTDOWN IDF FAIL Shut Down on IDF Failure Yes/No Yes FATALFAN
SHUTDOWN VFD HAND VFD Hand Mode Shutdown? Yes/No Yes HANDSHUT
VFD IN REVERSE? IDF VFD Motor In Reverse Yes/No
No (sizes 04-12)
Yes (sizes 14-
26)
VFD1MDIR
IDF VFD PARAMETERS
Indoor Fan VFD Settings
Menu
IDF VFD NOM. HP IDF VFD Motor HP 1 to 26 HP
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 14-26)
MOTPWRH
P
Table AC — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT ENTRY
CONTROL SET POINT AND CONFIGURATION LOG