181
INDOOR FAN (cont)
IDF VFD VOLTAGE IDF VFD Motor Volts 50 to 1000 V
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 14-26)
MOTVOLT
IDF VFD NOM. FREQ IDF VFD Motor Freq. 20 to 400 Hz 60 MOTFREQ
IDF VFD NOM. AMPS IDF VFD Motor Current 0.1 to 40 A
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 14-26)
MOTCUR
IDF VFD NOM. RPM IDF VFD Motor Nom. RPM 100 to 60000 rpm
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 14-26)
MOTNOMS
P
IDF VFD MIN REF IDF Danfoss Min Ref 0 to 65 Hz 0 MINREF
IDF VFD MAX REF IDF Danfoss Max Ref 0 to 65 Hz 60 MAXREF
VFD ACCEL. TIME IDF VFD Accel. Time 1 to 1800 sec 10 RAMPUP_T
VFD DECEL. TIME IDF VFD Decel. Time 1 to 1800 sec 10 RAMPDN_T
IDF VFD MAX AMPS IDF VFD Max Current 0 to 655.35 A
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 07-26)
VFD1MAXA
IDF VFD TIMEOUT IDF Danfoss Comm. TO 1 to 600 sec 30 CNT_TOUT
IDF VFD RESET DUR IDF Danfoss Auto Reset 0 to 600 sec 30 ARSTRT_T
VFD RFI FILTER IDF Danfoss RFI Filter On/Off On RFIFILTR
ECONOMIZER
Economizer Configurations
Menu
ECON INSTALLED? Economizer Installed? Yes/No
No: no FIOP
Yes: FIOP
ECONO
ECON MAX POS Econ Max Damper Position 0 to 100 % 100 DAMPMAX
ECON TRAVEL TIME Economizer Travel Time 5 to 300 sec 150 ECONOTRV
MINIMUM POSITION
CONFIGS
Minimum Position
Configurations Menu
MIN POS@ MAX FAN Econ Min at Max Fan Speed 0 to 100 % 30 MINP_MAX
MIN POS SPEED 1 Min Pos – User Speed 1 0 to 100 % 0 MP_USPD1
MIN POS DAMP 1 Min Pos – User Pos 1 0 to 100 % 0 MP_UPOS1
MIN POS SPEED 2 Min Pos – User Speed 2 0 to 100 % 0 MP_USPD2
MIN POS DAMP 2 Min Pos – User Pos 2 0 to 100 % 0 MP_UPOS2
MIN POS SPEED 3 Min Pos – User Speed 3 0 to 100 % 0 MP_USPD3
MIN POS DAMP 3 Min Pos – User Pos 3 0 to 100 % 0 MP_UPOS3
FREE COOL CONFIGS
Free Cooling Specific
Configurations Menu
LOW COOL SAT SP Low Free Cool SAT Setpnt 40 to 80 °F 65 LCSASP
HIGH COOL SAT SP High Free Cool SAT Setpnt 40 to 80 °F 55 HCSASP
FREE COOL MAX OAT Free Cooling Max OAT 0 to 90 °F 65 MAXFREET
FREE COOL MIN OAT Free Cooling Min Temp -30 to 70 °F 0 MINFREET
DIFF DRY BULB CTL Diff. Dry Bulb Control Enable/Disable Disable DIFFBULB
DIFF DB DEADBAND Diff. Dry Bulb Deadband 0 to 20 °F 3 OATRATDB
ENTHALPY HI LIMIT Max Enthalpy OA Limit 1.0 to 99.0 Btu/lb 28 FREEMAXE
Table AC — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT ENTRY
CONTROL SET POINT AND CONFIGURATION LOG