PRESSURES
Gas Inlet Pressure in. wg (48LC) ____________ in. wg
Gas Manifold Pressure (48LC) STAGE 1 _____________ in. wg
STAGE 2 _____________ in. wg
Refrigerant Suction CIRCUIT A _____________ PSIG
CIRCUIT A (superheat) _____________ °F
Refrigerant Discharge CIRCUIT A _____________ PSIG
CIRCUIT A (subcooling) _____________ °F
Verify Refrigerant Charge using Charging Charts (Y/N) _____
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped) (Y/N) _____
IV. HUMIDI-MIZER
®
SYSTEM START-UP
STEPS
1. Start unit In cooling (Close Y1) (Y/N) _____
OBSERVE AND RECORD
A. Suction pressure _______________ PSIG
B. Discharge pressure _______________ PSIG
C. Entering air temperature _______________ ° F
D. Leaving air temperature _______________ ° F
2. Switch unit to mixed cool and reheat mode (subcool) (Y/N) _____
OBSERVE
A. Reduction in suction pressure (5 to 7 psi expected) (Y/N)_____
B. Discharge pressure unchanged (Y/N) _____
C. Delta temperature decreases, close to neutral air (Y/N) _____
3. Switch unit to hot gas reheat mode.
OBSERVE
A. Suction pressure increases to normal cooling level
B. Discharge pressure decreases (35 to 50 psi) (Limited by head pressure control)
C. Liquid temperature returns to normal cooling level
4. With unit in dehumid mode switch to heating and verify compressor and outdoor fan stop (Y/N) _____
5. Turn off heating, cooling, and reheat, restore set points for thermostat and humidistat (Y/N) _____
REPEAT PROCESS FOR 2 COMPRESSOR SYSTEMS