93
CLOCK (cont)
DST STOP MONTH DST Stop Month
1=JANUARY,
2=FEBRUARY,
3=MARCH,
4=APRIL,
5=MAY,
6=JUNE,
7=JULY,
8=AUGUST,
9=SEPTEMBER,
10=OCTOBER,
11=NOVEBER,
12=DECEMBER
1=JANUARY STOPM
DST STOP WEEK DST Stop Week 1 to 5 1 STOPW
DST STOP DAY DST Stop Day
1=MONDAY,
2=TUESDAY,
3=WEDNESDAY,
4=THURSDAY,
5=FRIDAY,
6=SATURDAY,
7=SUNDAY
7=SUNDAY STOPD
DST MINS TO SUB DST Minutes to Subtract 0 to 90 min 60 MINSUB
START TIME IN DAY Time in day to start DST 0 to 600 min 120 DST_TOD
SCHEDULES Schedules Adjustment Menu
SCHEDULE NUMBER CCN Schedule Number
0 = Always Occupied,
1-64 = Local
Schedule,
65-99 = Global
Schedule
0=Always Occupied SCHEDNUM
OCCUPANCY SCHEDULE OCCUPANCY SCHEDULE DATA
HOLIDAYS Holiday Adjustment Menu
ALLOW G. HOLIDAY? Accept Global Holidays? Yes/No No HOLIDAYT
TIMED OVR LENGTH Timed Override Duration 0 to 4 hours 4 OTL_CFG
UNIT CONFIGURATIONS Unit Configurations Menu
GENERAL General Unit Configurations Menu
STARTUP DELAY Unit Startup Delay 10 to 600 sec 30 STARTDLY
UNIT CONTROL TYPE Unit Control Type
0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=TSTAT CTRLTYPE
THERMOSTAT TYPE Thermostat Hardware Type
0=CONV 2C2H,
1=DIGI 2C2H,
2=CONV 3C2H,
3=DIGI 3C2H
4=DIGI 2C2H_S
2=CONV 3C2H STATTYPE
ADAPTIVE TSTAT Tstat Adaptive Staging Yes/No Yes ADPTSTAT
DIRTY FILTER TIME Change Filter Timer 0 to 9999 hours 600 FILTLIFE
TEST MODE TIMEOUT Test inactivity time out
0=Disabled,
1=30 minutes,
2=1 hour,
3=2 hours,
4=4 hours,
5=8 hours,
6=12 hours
4=4 hours TEST_ITO
CCH MAX TEMP CCH Max Temperature 40 to 90 °F 65 CCHMAXT
STD BARO PRESSURE Std Barometric Pressure 13.00 to 35.00 in. Hg 29.92 STD_BARP
LINK STAGEUP TIME Linkage Stage inc. time 60 to 600 sec 180 LSTAGINC
UNIT’S MAX SAT Unit’s Maximum SAT 130 to 210 °F 200 UMAX_SAT
AUTO SAT FAULTS? Auto Clr SAT Limit Fault Yes/No No SATLACLR
ADAPTIVE TCS? Adaptive Temp Comp Start Enable/Disable Enable TCS_CFG
USER TCS BIASTIME User TCS Start bias time 0 to 180 min 0 TCSUBIAS
SWITCH INPUTS CONFIGS DI Config Menu
FIRE SHUTDOWN SW Fire Shutdown Switch
0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
2: no FIOP
0: FIOP
FIRE_CFG
HUMSTAT CHANNEL Humidistat Status Channel
0=None,
1=MBB DI12,
2=MBB DI13.
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB Di01
0=for all except
Humidimizer
6=Humidimizer Units
HUMDCHAN
HUMSTAT SW TYPE Humidistat Switch Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN HUMD_CFG
Table B — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT
APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY