94
UNIT CONFIGURATIONS (cont)
FILTER SW CHANNEL Filter Status Sw Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None FILTCHAN
FILTER SW TYPE Filter Status Switch Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN FILT_CFG
REMOTE OCC CHAN Remote Occupancy Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None RMOCCHAN
REMOTE OCC TYPE Remote Occupancy Sw Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN RMOC_CFG
REM.SHUTDOWN CHAN Remote Shutdown Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ROFFCHAN
REM.SHUTDOWN SW T Remote Shutdown Sw Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN ROFF_CFG
REM.SHUTDOWN TYPE Remote Shutdown ALM Type
0=Normal,
1=Emergency
0=Normal ROFFTYPE
COFS CHANNEL COFS Assigned Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None (no FIOP)
4=MBB DI02 (FIOP)
COFSCHAN
COFS TYPE COFS Switch Type
0=NORM OPEN,
1=NORM CLSD
1=NORM CLSD COFS_CFG
GEN STATUS CHAN General Status Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None GEN_CHAN
GEN STAT SW TYPE General Status Sw Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN GENS_CFG
SHUTDOWN GEN STAT General Status shutdown? Yes/No Yes GENFATAL
ENTHALPY SW CHAN Enthalpy Sw Channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ENTHCHAN
ENTHALPY SW TYPE Enthalpy Switch Type
0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN ENTH_CFG
IAQ OVERIDE SW CH IAQ override sw channel
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB DI01
IAQOCHAN
IAQ OVRRD SW TYPE IAQ Override Switch Type
0=NORM OPEN,
1=NORM CLSD
IAQOSCFG
ANALOG INPUT CONFIGS Analog Inputs Configuration Menu
SPRH SENS CHANNEL SPRH Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
4=SIOB AI10
0=None SPRHCHAN
SPRH RH @ 4MA SPRH Sensor Value at 4mA 0 to 100 % 0 SPRH_4MA
SPRH RH @ 20MA SPRH Sensor Value at 20mA 0 to 100 % 1 SPRH20MA
IAQ SENSOR CHAN IAQ Assigned Channel
0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: no FIOP
1: FIOP
IAQ_CHAN
IAQ PPM@ 4MA IAQ Sensor Value at 4mA 0 to 5000 ppm 0 IAQ_4MA
IAQ PPM@ 20MA IAQ Sensor Value at 20mA 0 to 5000 ppm 2000 IAQ_20MA
Table B — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT
APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY