EasyManua.ls Logo

Carrier 48NLT - Cooling System Start-Up

Carrier 48NLT
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start-Up
Cooling
Section
and
Make
Adjustments
A
CAUTION
Complete
the
required
procedures
given
in
the
Pre-Start-
Up
section
before
starting
the
unit.
Do
not
jumper
any
safety
devices
when
operating
the
unit.
Do
not
operate
the
compressor
when
the
outdoor
tem¬
perature
is
below
55
F
(unless
accessory
low-temperature
kit
is
installed).
Do
not
rapid-cycle
the
compressor.
Allow
5
minutes
between
“on”
cycles
to
prevent
compressor
damage.
CHECKING
COOLING
CONTROL
OPERATION
-
Start
and
check
the
unit
for
proper
cooling
control
operation
as
follows:
1.
Place
room
thermostat
SYSTEM
switch
in
OFF
posi¬
tion.
Observe
that
blower
motor
starts
when
FAN
switch
is
placed
in
ON
position
and
shuts
down
when
FAN
switch
is
placed
in
AUTO,
position.
2.
Place
SYSTEM
switch
in
COOL
position
and
FAN
switch
in
AUTO,
position.
Set
cooling
control
below
room
tem¬
perature.
Observe
that
compressor,
condenser
fan
and
evaporator
blower
motors
start.
Observe
that
cooling
cycle
shuts
down
when
control
setting
is
satisfied.
The
blower
motor
has
an
off
delay
of
approximately
one
minute
on
shutdown.
3.
When
using
an
auto.-changeover
room
thermostat,
place
both
SYSTEM
and
FAN
switches
in
AUTO,
positions.
Observe
that
unit
operates
in
heating
mode
when
tem¬
perature
control
is
set
to
“call
for
heating”
(above
room
temperature)
and
operates
in
cooling
mode
when
tem¬
perature
control
is
set
to
“call
for
cooling”
(below
room
temperature).
CHECKING
AND
ADJUSTING
REFRIGERANT
CHARGE
The
refrigerant
system
is
fully
charged
with
R-22
refrig¬
erant,
tested
and
factory-sealed.
NOTE:
Adjustment
of
the
refrigerant
charge
is
not
required
unless
the
unit
is
suspected
of
not
having
the
proper
R-22
charge.
For
all
applications,
the
correct
R-22
charge
for
the
best
performance
is
the
charge
that
results
in
a
suction
gas
superheat
of
5
F
at
the
compressor
inlet
when
the
unit
is
operating
at
the
ARI
rating
conditions
of
95
F
dry-bulb
(db)
outdoor
and
80
F
db/67
F
wet-bulb
(wb)
indoor.
A
superheat
charging
label
is
attached
to
the
outside
of
the
compressor
access
door.
The
label
includes
a
“Super¬
heat
Charging
Table”
and
a
“Required
Suction-Tube
Tem¬
perature
(F)”
chart.
An
accurate
superheat
thermocouple-
or
thermistor-type
thermometer,
a
sling
psychrometer
and
a
gage
manifold
are
required
when
using
the
superheat
charging
method
for
eval¬
uating
the
unit
charge.
Do
not
use
mercury
or
small
dial-
type
thermometers
because
they
are
not
adequate
for
this
type
of
measurement.
A
CAUTION
When
evaluating
the
refrigerant
charge,
an
indicated
adjustment
to
the
specified
factory
charge
must
always
be
very
minimal.
If
a
substantial
adjustment
is
indi¬
cated,
an
abnormal
condition
exists
somewhere
in
the
cooling
system,
such
as
insufficient
airflow
across
either
coil
or
both
coils.
Proceed
as
follows:
1.
R
emove
caps
from
low-
and
high-pressure
service
fittings.
2.
Using
hoses
with
valve
core
depressors,
attach
low-
and
high-pressure
gage
hoses
to
low-
and
high-pressure
ser¬
vice
fittings,
respectively.
3.
Start
unit
in
cooling
mode
and
let
unit
run
until
system
pressures
stabilize.
4.
Measure
and
record
the
following.
a.
Outdoor
ambient-air
temperature
(F
db).
b.
Evaporator
inlet-air
temperature
(F
wb).
c.
Suction-tube
temperature
(F)
at
low-side
service
fitting.
d.
Suction
(low-side)
pressure
(psig).
5.
Using
“Superheat
Charging
Table,”
compare
outdoor-
air
temperature
(F
db)
with
evaporator
inlet-air
temper¬
ature
(F
wb)
to
determine
desired
system
operating
su¬
perheat
temperature.
See
Table
6.
6.
Using
“Required
Suction-Tube
(F)”
table,
compare
de¬
sired
superheat
temperature
with
suction
(low-side)
operating
pressure
(psig)
to
determine
proper
suction-
tube
temperature.
See
Table
7.
7.
Compare
actual
suction-tube
temperature
with
proper
suction-tube
temperature.
Using
a
tolerance
of
±
3
F,
add
refrigerant
if
actual
temperature
is
more
than
3
F
higher
than
proper
suction-tube
temperature,
or
remove
refrigerant
if
actual
temperature
is
more
than
3
F
lower
than
required
suction-tube
temperature.
NOTE:
If
the
problem
causing
the
inaccurate
readings
is
a
refrigerant
leak,
refer
to
Start-Up,
Check
for
Refrigerant
Leaks
section.
INDOOR
AIRFLOW
AND
AIRFLOW
ADJUSTMENTS
A
CAUTION
For
cooling
operation,
the
recommended
airflow
is
350
to
450
cfm
per
each
12,000
Btuh
of
rated
cooling
ca¬
pacity.
For
heating
operation,
the
airflow
must
pro¬
duce
a
temperature
rise
that
falls
within
the
range
stamped
on
the
unit
rating
plate.
Direct-drive
blower
motors
are
factory
connected
to
de¬
liver
the
proper
heating
and
cooling
airflows
at
normal
ex¬
ternal
static
pressures
(medium
speed
cooling,
low
speed
heating
for
230-v
units)
and
high
speed
cooling
(units
with
460-v
have
medium
speed
cooling
and
high
speed
heating).
For
208-V
operation
on
208/230-v
rated
direct
drive
units,
interchange
motor
leads
to
high
speed
for
cooling
and
medium
speed
for
heating
operation.
Table
5
shows
the
temperature
rise
at
various
airflow
rates.
Tables
8
and
9
show
both
heating
and
cooling
airflows
at
various
external
static
pressures.
Refer
to
these
tables
to
determine
the
airflow
for
the
system
being
installed.
NOTE:
Be
sure
that
all
supply-
and
return-air
grilles
are
open,
free
from
obstructions
and
adjusted
properly.
A
WARNING
Disconnect
electrical
power
to
the
unit
before
changing
blower
speed.
(Be
sure
to
turn
off
gas
supply
before
disconnecting
electrical
power.)
Electrical
shock
can
cause
personal
injury
or
death.
A
CAUTION
Do
not
change
the
blower-motor
lead
connections
on
460-v
units
from
the
factory
setting.
Damage
to
unit
may
result.
16

Related product manuals