Carrier 48NLT - Page 18

Carrier 48NLT
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
8
Dry
Coil
Air
Delivery
{Cfm)*
at
Indicated
External
Static
Pressure
and
Voltage
-
Horizontal
Discharge
(Without
Filter)
48
V-PH-HZ
MOTOR
SPEED
208
V
230
V
or
460
V
in.
wg
0.0
0.3
0.4
0.5
0.0
0.1
WEm\
0.4
0.5
NLT018,
NLT024,
NHT024
208/230-1-60
Lowt,
Med*
**
Watts
451
427
407
383
365
348
501
477
457
433
415
398
Cfm
1185
1129
1088
1026
979
922
1256
1195
1148
1081
1031
971
Hi
Watts
511
483
464
440
420
402
561
533
514
490
470
452
Cfm
1370
1291
i
1221
1142
1063
1003
1442
1359
1285
I
1202
1119
1056
NLT030,
NMT030
208/230-1-60
Lowt,
Med**
Watts
519
507
492
477
455
431
569
557
542
527
505
481
Cfm
1184
1163
1150
1134
1105
1064
1248
1226
1211
1194
1164
mm
Hi
Watts
620
602
581
559
532
493
670
652
631
609
582
Cfm
1443
1414
1376
1329
1279
1197
1519
1489
1449
1399
1347
1261
NHT030,
NLT036
NMT036,
NLT042
NMT042
208/230-1-60
208/230-3-60,
460-3-60tt
Lowt,
Med**
Watts
I
560
544
527
505
482
461
610
593
575
500
524
494
Cfm
1515
1452
1389
1308
1227
1105
1597
1530
1464
1378
1293
1164
Hi
Watts
670
650
631
602
573
542
720
701
680
653
625
594
Cfm
1765
1705
1621
1521
1383
1254
1857
1795
1708
1603
1457
1321
NET036,
042
208/230-1-60
208/230-3-60
460-3-60tt
Lowt,
Med**
Watts
873
847
814
785
758
734
987
945
911
877
850
809
Cfm
1717
1690
1645
1597
1550
1496
1979
1922
1859
1802
1734
1667
Hi
Watts
1075
1030
995
960
930
900
1121
1087
1046
1017
981
952
Cfm
2119
2062
1995
1913
1863
1793
2135
2066
1998
1931
1858
1795
NHT036,
NVT036
NHT042,
NVT042
208/230-1-60
208/230-3-60
460-3-60tt
Lowt,
Med**
Watts
740
700
660
615
580
540
755
725
680
650
610
575
Cfm
1913
1820
1736
1645
1544
1428
1976
1909
1806
1714
1603
1495
Hi
Watts
790
760
720
690
650
610
850
820
780
750
715
675
Cfm
2032
1942
1844
1759
1636
1514
2086
1983
1883
1782
1665
1545
NLT048,
NMT048
NHT048
208/230-1-60
208/230-3-60
460-3-60tt
Lowt,
Med**
Watts
770
730
690
650
610
575
810
765
730
695
655
610
Cfm
1945
1880
1796
1708
1611
1508
2061
1970
1892
1813
1704
Hi
Watts
850
810
770
730
690
655
890
855
820
780^
750
715
Cfm
2138
2045
1943
1846
1738
1624
2178
2081
1941
1869
1769
1650
NVT048
208/230-1-60
208/230-3-60
460-3-60tt
Lowt,
Med**
Watts
985
950
915
890
860
820
1095
1055
1010
975
935
890
Cfm
1931
1901
1862
1813
1768
1703
2183
2125
2071
2005
1931
1854
Hi
Watts
1220
1165
1130
1080
1035
995
1300
1265
1220
1180
1120
Cfm
2376
2311
2244
2170
2083
2003
2511
2431
2359
2271
2168
NLT060,
NIVFT060
I
NHT060,
NVT060
208/230-1-60
208/230-3-60
460-3-60tt
Lowt,
Med**
Watts
1125
1055
1015
980
940
905
1205
1125
1095
1060
1030
990
Cfm
2184
2125
2063
2000
1938
1880
2285
2225
2163
2106
2045
1980
Hi
Watts
1220
1175
1125
1080
1040
1005
1300
1250
1210
1165
1130
1085
Cfm
2380
2307
2262
2165
2095
2024
2487
2412
2335
2260
2179
2110
*Air
delivery
values
are
without
air
filter
and
are
for
dry
coil.
See
Table
10
for
wet
coll
pressure
drop.
Deduct
field-supplied
air
filter
pressure
drop
and
wet
coil
pressure
drop
to
obtain
external
static
pressure
available
for
ducting.
tFactory
blower-motor
speed
setting
for
heating
operation.
**Factory
blower-motor
speed
setting
for
cooling
operation.
ttDo
not
change
blower
speed
settings
for
units
with
460-v
(high
speed
only).
NOTE:
Do
not
operate
the
unit
at
a
cooling
airflow
that
is
less
than
350
cfm
per
each
12,000
Btuh
of
rated
cooling
capacity.
Evaporator
coil
Icing
may
occur
at
airflows
below
this
point.
Water
blow-off
may
occur
at
airflows
above
450
cfm
per
12,000
Btuh
of
rated
cooling
capacity
The
heating
and/or
cooling
airflow
of
208/230-v
direct-
drive
blower
motors
can
be
changed
by
changing
the
lead
connections
of
the
blower
motor.
The
motor
leads
are
color-
coded
as
follows:
black
=high
speed
blue
=
medium
speed
red
=low
speed
NOTE:
For
all
208/230-v
direct-drive
units,
the
red
motor
lead
connected
to
the
heat
relay
(L)
on
PCI
blower
control
determines
the
heating
speed
and
resulting
airflow,
and
the
blue
motor
lead
connected
to
the
cooling
relay
(H)
on
PCI
blower
control
determines
the
cooling
speed
and
resulting
airflow.
See
the
unit
wiring
label.
To
change
the
heating
and/or
cooling
speed
of
a
direct-
drive
motor,
connect
the
appropriate
color-coded
lead
at
blower
motor
connector
to
speed-tap
desired.
(See
unit
wiring
label.)
When
installing
a
208-
or
230-v
direct-drive
unit
that
is
factory
connected
for
heating
and
cooling
speeds
that
are
not
the
same,
and
the
same
speed
for
both
heating
and
cool¬
ing
is
required
for
a
particular
application,
disconnect
red
lead
at
terminal
L
of
heat
relay
and
connect
to
terminal
MI
on
PCI
blower
control.
Connect
a
field-supplied
jumper
be¬
tween
terminal
L
on
heat
relay
and
terminal
H
of
cooling
relay.
Connect
blue
lead
at
blower
motor
to
appropriate
speed
tap.
18