EasyManua.ls Logo

Carrier 48SS018 - Certified Dimension Print; Required Clearances for Servicing; Required Clearances to Combustible Material; NEC (National Electrical Code) Required Clearances

Carrier 48SS018
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CERTIFIED DIMENSION PRINT
OUTDOOR COIL
INDOOR COIL
INDOOR COIL ACCESS
REQ’D CLEARANCES FOR SERVICING in. (mm)
Duct Panel ........................0
Unit Top .....................36(914.4)
Side Opposite Ducts ..............36(914.4)
Compressor Access ..............36(914.4)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L
in. (mm)
Maximum Extension of Overhangs ......48(1219.2)
Unit Top .....................14(355.6)
Duct Side of Unit .................2(50.8)
Side Opposite Ducts ..............14(355.6)
Bottom of Unit ......................0
Flue Panel ...................36(914.4)
NEC (National Electrical Code) REQ’D CLEARANCES
in. (mm)
Between Units, Control Box Side .......42(1066.8)
Unit and Ungrounded Surfaces,
Control Box Side ...............36(914.4)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side . . . 42 (1066.8)
UNIT
48SS
ELECTRICAL
CHARACTERISTICS
UNIT
WEIGHT
CORNER WEIGHT
(lb/kg)
lbkgABCD
018040 208/230-1-60 272 123 81/37 62/28 76/35 53/24
024040 208/230-1-60 303 138 97/44 43/20 123/56 40/18
024060 208/230-1-60 315 143 100/45 46/21 126/57 43/20
030040 208/230-1-60 320 145 100/45 47/21 126/57 47/21
030060/080 208/230-1-60 324 147 94/43 63/29 115/52 52/24
036060/080 208/230-1-60 336 153 86/39 76/35 111/50 63/29
036100/120 208/230-1-60 348 158 89/40 79/36 114/52 66/30
042060/080 208/230-1-60 375 170 95/43 86/39 119/54 75/34
042100/120 208/230-1-60 387 176 98/45 89/40 122/55 78/35
UNIT
48SS
UNIT
HEIGHT
(in./mm)
DIMENSION
(in./mm)
CENTER OF GRAVITY
(in./mm)
EFGXYZ
018040 24.12/612.8 16
9
16
/420.7 18
15
16
/481.0 25.07/637 20.59/523 10.85/276
024040 24.12/612.8 16
9
16
/420.7 18
15
16
/481.0 27.07/688 23.35/693 10.85/276
024060 24.12/612.8 16
9
16
/420.7 18
15
16
/481.0 26.98/685 23.27/591 10.85/276
030040 24.12/612.8 16
9
16
/420.7 18
15
16
/481.0 26.71/678 23.46/596 10.85/276
030060/080 24.12/612.8 16
9
16
/420.7 18
15
16
/481.0 27.15/689 22.36/568 10.85/276
036060/080 24.12/612.8 16
9
16
/420.7 18
15
16
/481.0 27.50/698 22.48/571 10.85/276
036100/120 24.12/612.8 16
9
16
/420.7 18
15
16
/481.0 27.40/696 22.44/570 10.85/276
042060/080 28.12/714.2 20
9
16
/522.3 22
15
16
/582.6 27.01/686 22.44/570 12.65/321
042100/120 28.12/714.2 20
9
16
/522.3 22
15
16
/582.6 26.94/684 22.44/570 12.65/321
NOTE: Clearances must be maintained to prevent recircu-
lation of air from outdoor fan discharge.
3