CERTIFIED DIMENSION PRINT
INDOOR COIL
OUTDOOR COIL
INDOOR COIL ACCESS
REQ’D CLEARANCES FOR SERVICING in. (mm)
Duct Panel ........................0
Unit Top .....................36(914.4)
Side Opposite Ducts ..............36(914.4)
Compressor Access ..............36(914.4)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L
in. (mm)
Maximum Extension of Overhangs ......48(1219.2)
Unit Top .....................14(355.6)
Duct Side of Unit .................2(50.8)
Side Opposite Ducts ..............14(355.6)
Bottom of Unit ......................0
Flue Panel ...................36(914.4)
NEC (National Electrical Code) REQ’D CLEARANCES
in. (mm)
Between Units, Control Box Side .......42(1066.8)
Unit and Ungrounded Surfaces,
Control Box Side ...............36(914.4)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side . . . 42 (1066.8)
UNIT
48SS
ELECTRICAL
CHARACTERISTICS
UNIT
WEIGHT
CORNER WEIGHT
(lb/kg)
lbkgABCD
048080 208/230-1-60 414 188 107/49 83/38 158/72 66/30
048100/120/140 208/230-1-60 426 193 110/50 86/39 159/72 71/32
060080 208/230-1-60 453 206 117/53 93/42 167/76 76/35
060100/120/140 208/230-1-60 465 211 120/55 96/44 167/76 82/37
UNIT
48SS
CENTER OF GRAVITY
(in./mm)
XYZ
048080 28.76/731 23.46/596 15.35/390
048100/120/140 28.42/722 23.42/595 15.35/390
060080 28.36/720 23.27/591 15.35/390
060100/120/140 27.95/710 23.23/590 15.35/390
NOTE: Clearances must be maintained to prevent recircu-
lation of air from outdoor fan discharge.