37
PREMIERLINK] CONTROL
C08199
Fig. 44 PremierLinkt Controller
The PremierLink controller (see Fig. 44) is compatible
with Carrier Comfort Network (CCN) devices. This
control is designed to allow users the access and ability to
change factorydefined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilot (TM), Touch Pilot (TM)
and Service Tool. (Standard tier display tools Navigator
and Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).)
The PremierLink control is factorymounted in the
48TC unit’s main control box to the left of the LCTB.
Factory wiring is completed through harnesses connected
to the LCTB thermostat. Field connections are made at a
16pole terminal block (TB1) located on the bottom shelf
of the unit control box in front of the PremierLink
controller The factoryinstalled PremierLink control
includes the supplyair temperature (SAT) sensor. The
outdoor air temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$er 2 package.