EasyManua.ls Logo

Carrier 48TC 28 Series - Page 48

Carrier 48TC 28 Series
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48
Table 15 – Altitude Compensation* (17 30) – Natural Gas
NATURAL GAS NOMINAL HEAT INPUT
ELEVATION 220k BTUH 310k BTUH 400k BTUH
Feet Meters
Orifice
Size
Input
(btu/hr)
Orifice
Size
Input
(btu/hr)
Orifice
Size
Input
(btu/hr)
0 - 2000
0-610 30 220,000 30 310,000 30 400,000
2000 610 30 202,400 30 285,200 30 368,000
3000 914 31
1
193,600 31
1
272,800 31
1
352,000
4000 1219 31
1
184,800 31
1
260,400 31
1
336,000
5000 1524 31
1
176,000 31
1
248,000 31
1
320,000
6000 1829 31
1
167,200 31
1
235,600 31
1
304,000
7000 2134 32
1
158,400 32
1
223,200 32
1
288,000
8000 2438 32
1
149,600 32
1
210,800 32
1
272,000
9000 2743 34
1
140,800 34
1
198,400 34
1
256,000
10000 3048 35
2
132,000 35
1
186,000 35
1
240,000
11000 3353 37
2
123,200 37
2
173,600 37
2
224,000
12000 3658 37
2
114,400 37
2
161,200 37
2
208,000
13000 3962 39
2
105,600 39
2
148,800 39
2
192,000
14000 4267 39
2
96,800 39
2
136,400 39
2
176,000
Table 16 – Altitude Compensation* (17 30) – Propane Gas
PROPANE GAS NOMINAL HEAT INPUT
ELEVATION 220k BTUH 310k BTUH 400k BTUH
Feet Meters
Orifice
Size
Input
(btu/hr)
Orifice
Size
Input
(btu/hr)
Orifice
Size
Input
(btu/hr)
0 - 2000
0-610 48
5
220,000 48
5
310,000 48
5
400,000
2000 610 49
3
202,400 49
3
285,200 49
3
368,000
3000 914 49
3
193,600 49
3
272,800 49
3
352,000
4000 1219 49
3
184,800 49
3
260,400 49
3
336,000
5000 1524 50
3
176,000 50
3
248,000 50
3
320,000
6000 1829 50
3
167,200 50
3
235,600 50
3
304,000
7000 2134 50
3
158,400 50
3
223,200 50
3
288,000
8000 2438 51
3
149,600 51
3
210,800 51
3
272,000
9000 2743 51
3
140,800 51
3
198,400 51
3
256,000
10000 3048 52
4
132,000 52
4
186,000 52
4
240,000
11000 3353 52
4
123,200 52
4
173,600 52
4
224,000
12000 3658 53
4
114,400 53
4
161,200 53
4
208,000
13000 3962 53
4
105,600 53
4
148,800 53
4
192,000
14000 4267 53
4
96,800 53
4
136,400 53
4
176,000
* As the height above sea level increases, there is less oxygen per cubic ft. of air. Therefore, heat input rate should be reduced
at higher altitudes.
XX
1
= CRNGELEV001A00
XX
2
= CRNGELEV002A00
XX
3
= CRLPELEV006A00
XX
4
= CRLPELEV006A00
XX
5
= CRLPKIT9001A00

Related product manuals