26
Table 5 — Fan Rpm at Motor Pulley Settings*
*Approximate fan rpm shown.
†Indicates alternate motor and drive package.
**Indicates high-static motor and drive package.
††Indicates standard motor and drive package.
UNIT 48TF,TM
MOTOR PULLEY TURNS OPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
6
004† 1000 976 952 928 904 880 856 832 808 784 760 ——
004** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075
005† 1185 1150 1115 1080 1045 1010 975 940 905 870 835 ——
005** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075
006† 1300 1260 1220 1180 1140 1100 1060 1020 980 940 900 ——
006** 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 ——
007†† 1460 1420 1380 1345 1305 1265 1225 1185 1150 1110 1070 ——
007** 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 ——
MOTOR MOUNTING
PLATE NUTS
0
1000
2000
3000
4000
5000
6000
0.05 0.10 0.15 0.20 0.25 0.30 0.35
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
Static Pressure (in. wg)
0
1000
2000
3000
4000
5000
6000
0.1" 0.2" 0.3" 0.4"
Flow in cubic feet per minute
(cfm)
Fig. 36 — Vertical EconoMi$er2 Static Pressure
(48TF,TM004-007)
Fig. 37 — Horizontal EconoMi$er2 Static Pressure
(48TF,TM004-007)
Fig. 38 — Direct Drive Motor Mounting
Fig. 39 — Belt Drive Motor Mounting
Fig. 40 — Evaporator-Fan Pulley Adjustment