EasyManua.ls Logo

Carrier 48TF004-007 - Typical Wiring Schematic and Component Arrangement

Carrier 48TF004-007
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56
LEGEND FOR FIG. 54 TYPICAL WIRING SCHEMATIC AND COMPONENT ARRANGEMENT
IMPORTANT: Refer to unit wiring label for actual unit wiring
information.
AHA
Adjustable Heat Anticipator
C
Contactor, Compressor
CAP
Capacitor
CC
Cooling Compensator
COMP
Compressor Motor
ECON
Economizer
EQUIP
Equipment
FPT
Freeze Up Protection Thermostat
GND
Ground
HPS
High-Pressure Switch
HS
Hall-Effect Sensor
I
Ignitor
IDM
Induced-Draft Motor
IFC
Indoor Fan Contactor
IFM
Indoor (Evaporator) Fan Motor
IGC
Integrated Gas Unit Controller
LED
Light-Emitting Diode
LPS
Low-Pressure/Loss-of-Charge Switch
LS
Limit Switch
MGV
Main Gas Valve
MTR
Motor
OFM
Outdoor (Condenser) Fan Motor
OLR
Overload Relay
PL
Plug Assembly
QT
Quadruple Terminal
R
Relay
RS
Rollout Switch
SAT
Supply-Air Thermostat
SEN
Sensor
SW1
Switch Fully Open
SW2
Switch Fully Closed
SW3
Switch Min. Vent Position
SW4
Switch Max. Vent Position
TC
Thermostat-Cooling
TDR
Time-Delay Relay
TH
Thermostat-Heating
TRAN
Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only;
not to represent wiring.
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire
or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostat: HH07AT170, 172, 174 and P272-2783 Subbase: HH93AZ176, 178 and
P272-1882, 1883.
4. Set heat anticipator at .14 amp. For units with 2 stages of heating, set stage two anticipator at
.14 amp.
5. Use copper conductors only.
6. TRAN is wired for 230-v unit. If unit is to be run with 208-v power supply, disconnect BLK wire
from 230-v tap (ORN) and connect to 208-v tap (RED). Insulate end of 230-v tap.

Table of Contents

Related product manuals