Outdoor
Air
Intake
(50CD008)
The
50CD
can
be
equipped
with
an
optional
outdoor
air
damper
or
an
economizer
that
mixes
outdoor
air
with
return
air.
Field-Fabricated
Ductwork
50CD
See
Fig.
3.
Secure
all
ducts
to
roof
curb
and
building
structure
before
unit
is
placed
on
curb.
Do
not
connect
ductwork
to
unit.
Cabinet
return
air
static
shall
not
exceed
0.35
in.
with
economzier
or
0.40
in.
without
economizer.
50CH
See
Fig.
4.
Secure
all
ductwork
to
flanges
on
unit
supply
air
and
return
air
openings
and
building
structure.
50CD/CH
Insulate
and
weatherproof
all
ex¬
ternal
ductwork,
joints
and
roof/
wall
openings
with
flashing
and
mastic
in
accordance
with
applicable
codes.
Insulate
ducts
passing
thru
an
unconditioned
space
and
cover
with
a
vapor
barrier.
A
minimum
clearance
is
not
required
for
any
air
duct
installation.
Optional
Manual
Outdoor
Air
Damper
(50CD
008)
Optional
outdoor
air
damper
is
shipped
with
hood
broken
down
in
unit
filter
section.
See
Fig.
5.
ASSEMBLY
1.
Remove
protective
polyethylene
cover
from
unit.
See
Fig.
5.
2.
Remove
upper
filter
access
panel
(save
screws).
See
Fig.
5.
3.
Remove
hood
parts
from
unit
evaporator
fan
and
filter
area.
Assemble
hood
top
and
side
plates
as
shown
in
Fig.
6.
Do
not
attach
hood
to
unit
at
this
time.
4.
Adjust
outdoor
air
damper
blade
to
desired
setting
for
outside
air
intake
by
releasing
linkage
rod
setscrew
and
adjusting
linkage
rod.
See
Fig.
7.
Secure
damper
blade
in
desired
position
with
setscrew.
5.
Remove
screws
holding
manual
outdoor
air
damper
to
unit.
See
Fig.
8.
6.
Install
outdoor
air
hood
assembly,
using
screws
from
step
5.
These
screws
secure
the
manual
outdoor
air
damper
assembly
and
the
outdoor
air
hood
to
unit.
See
Fig.
9.
7.
Slide
outdoor
air
inlet
screens
into
screen
tracks
on
hood
side
plates.
While
holding
screens
in
place,
fasten
screen
retainer
to
hood
using
screw
provided.
Make
sure
bottom
edge
of
screens
rest
inside
base
rail
as
shown
in
Fig.
9.
8.
Replace
upper
access
panel
with
screws
saved
from
step
2.
9.
To
check
percentage
of
ventilation
air
entering
unit,
proceed
as
follows:
a.
If
unit
power
is
on,
turn
it
off.
b.
Jumper
red
and
black
wires
in
24-v
barrier
in
main
control
box.
See
Fig.
10.
c.
Turn
on
unit
power
to
energize
evaporator
(indoor)
fan.
Fig.
6
Outdoor
Air
Hood
Details
d.
Check
percentage
of
ventilation
air
entering
unit.
If
percentage
varies
from
that
specified,
remove
upper
filter
access
panel
and
adjust
damper
blade
as
described
in
step
4.
Proce¬
dure
may
have
to
be
repeated
until
proper
percentage
of
ventilation
air
is
attained.
e.
Turn
off
power.
Remove
jumper
between
red
and
black
wires.
f.
Replace
upper
filter
access
panel.
50CH008
Unit
Assembly
Remove
packaging
and
tape
from
evaporator
fan
drive
system.
Evaporator
Air
Fan
Evaporator
fan
uses
a
belt-
drive
motor
which
provides
high
static
at
nominal
airflow.
The
standard
motor
provides
approxi¬
mately
0.95
in.
static
at
nominal
cfm
and
the
alter¬
nate
motor
provides
1.0
in.
static
at
nominal
cfm.
6