Table
4
Air
Quantity
Limits
UNIT
MODEL
MIN
CFM
MAX
CFM
50DPE014
3750
6250
50DP016
4500
7500*
50DP020
5400
9000
Mndoor
Fan
Max
Watts
=
3000
Indoor
Air
Fan
Fan
belts
and
pulleys
are
factory
installed.
Belts
are
secured
to
pulleys
with
tape.
Remove
tape
and,
if
required,
adjust
as
described
in
Service,
Indoor
Air
Fan
Adjustment.
50DP020
has
2
non-adjustable
pulleys.
Pulley
A
is
installed
in
unit.
Pulley
B
is
shipped
in
cardboard
box
taped
to
vestibule
below
main
control
box.
Outdoor
Air
Fans
and
Motors
are
factory
set.
Refer
to
Service,
Outdoor
Air
Fan
Adjustment
as
required.
Return
Air
Filters
Check
that
correct
filters
are
installed
in
filter
tracks.
See
Table
1.
Do
not
operate
unit
without
return
air
filters.
Outdoor
Air
Inlet
Screens
Outdoor
air
inlet
screens
must
be
in
place
before
operating
unit.
Economizer
Section
Remove
filter
access
panel.
Check
that
outdoor
air
damper
is
closed
and
return
air
damper
is
open.
Economizer
operation
and
adjustment
is
described
in
Start-Up,
Economizer
Operation;
and
Service,
Econo¬
mizer
Adjustment,
respectively.
Base
Unit
Operation
COOLING
Unit
power
on.
System
selector
switch
at
COOL;
fan
switch
at
AUTO.;
thermostat
at
a
setting
below
room
temperature.
50DPEQ14
and
50DP016
Compressor
starts
unloaded
on
closure
of
No.
1
contact
in
thermostat.
Additional
rise
in
room
temperature
closes
contact
No.
2
in
thermostat
which
de-energizes
the
unloader
coil.
Compressor
is
now
fully
loaded.
Check
cooling
effects
at
a
setting
below
room
tempera¬
ture.
Check
unit
charge.
Refer
to
Service,
Refrigerant
Charge.
Reset
thermostat
at
a
temperature
above
room
tem¬
perature.
Compressor(s)
will
shut
off.
50DP020
Upon
a
rise
in
room
temperature,
cooling
contact
No.
1
in
the
thermostat
closes,
energizing
the
first-stage
cooling
contactor
and
the
indoor
fan
con¬
tactor.
The
first-stage
compressor,
outdoor
fan
motor
and
indoor
fan
motor
start
and
run.
Upon
a
further
rise
in
room
temperature,
cooling
contact
No.
2
in
the
thermostat
closes,
energizing
the
second-stage
cooling
contactor.
The
second-stage
compressor
starts
and
runs.
To
Shut
Off
Unit
Set
system
selector
switch
at
OFF
position
or
reset
thermostat
above
room
temperature.
Units
with
Signal-LOC
protection
device
shut
down
on
any
safety
trip
and
thermostat
light
comes
on.
Determine
reason
for
safety
trip.
Restart
compressor(s)
by
resetting
circuit
breaker
at
unit.
HEATING
Turn
on
main
power
to
unit.
Set
system
selector
switch
at
HEAT,
fan
switch
at
AUTO.;
and
thermostat
at
a
setting
above
room
temperature.
First
stage
of
electric
heater
elements
are
energized
on
closing
of
heating
contact
No.
I
in
thermostat.
On
a
further
fall
of
room
temperature,
heater
contact
No.
2
closes
ener¬
gizing
second-stage
electric
heater
elements.
To
Shut
Off
Unit
Set
system
selector
switch
at
OFF.
VENTILATION
AIR
CIRCULATION
(Continuous
Fan)
Unit
power
on.
System
selector
switch
at
OFF,
HEAT
or
COOL;
fan
switch
set
at
ON.
Indoor
fan
con¬
tactor
is
energized
through
the
switch
on
the
thermostat,
and
the
indoor
fan
runs
continuously.
AUTOMATIC
CHANGEOVER
(with
Automatic
Changeover
Thermostat)
System
selector
switch
set
at
AUTO.
When
temperature
of
conditioned
space
rises
to
cooling
selector
lever
setting,
unit
automatically
switches
from
heating
mode
to
cooling
mode.
When
tem¬
perature
of
the
conditioned
space
falls
to
the
heating
selector
lever
setting,
unit
automatically
changes
from
cooling
mode
to
heating
mode.
The
thermostat
is
inter¬
locked
so
that
cooling
and
heating
systems
do
not
operate
at
the
same
time.
HEAD
PRESSURE
CONTROL
All
units
have
fan
cycling
thermostats
which,
at
55
F,
shut
off
one
outdoor
fan
motor.
This
permits
unit
to
operate
down
to
40
F
outdoor
air
temperature.
Economizer
Operation
If
unit
is
equipped
with
modulating
outdoor
air
control
(economizer),
it
should
operate
as
follows:
COOLING
MODE
Indoor
and
outdoor
fans
and
com¬
pressor
energize
when
there
is
a
call
for
cooling
and
enthalpy
of
outdoor
air
is
above
enthalpy
control
setting.
The
economizer
damper
moves
to
VENT
position.
Indoor
fan
starts
and
economizer
damper
opens
fully
on
a
first-stage
call
for
cooling
when
enthalpy
of
outdoor
air
is
below
the
enthalpy
control
setting.
Compressor
remains
off.
Compressor
is
energized
and
mechanical
cooling
integrates
with
economizer
cooling
upon
a
second-
stage
call
for
cooling.
If
outdoor
air
temperature
falls
below
50
F,
cooling
lockout
switch
prevents
compressor
from
operating.
Economizer
damper
modulates
when
mixed
air
tem¬
perature
is
below
mixed
air
thermostat
setting.
A
freeze
protection
thermostat
(FPT)
is
located
on
the
indoor
coil.
It
detects
ice
buildup
and
turns
off
the
compressor,
thus
allowing
the
coil
to
clear.
Once
ice
melts,
the
compressor
can
be
re-energized.
HEATING
MODE'
Outdoor
air
damper
stays
at
VENT
position
while
indoor
air
fan
runs.
NOTE:
If
fan
switch
is
at
ON
position,
and
room
thermo¬
stat
is
satisfied,
damper
goes
to
ventilation
position.
11