Variable
Volume
Units
Units
suitable
for
use
with
variable
volume
air
handling
systems
are
equipped
with
2
electric
unloaders
on
the
compressor.
The
control
panel
for
these
units
(Fig.
18)
consists
of
a
step
controller,
a
proportional
thermostat,
a
7-day
timer
and
a
power
switch.
Before
starting
unit,
open
compressor
service
valves
and
liquid
line
shutoff
valve.
Be
sure
compressor
crank¬
case
heaters
have
been
on
for
24
hours
and
that
crankcase
oil
level
indicates
half
full.
CONTROL
SEQUENCE
CHECKOUT
1.
Turn
on
unit
main
power
supply.
Be
sure
unit
is
ready
to
operate.
2.
Set
variable
volume
control
panel
POWER
switch
at
ON.
3.
If
supply
air
leaving
unit
is
above
50
F
(or
other
field-
set
temperature),
step
controller
will
operate
to
de¬
energize
compressor
unloader
solenoids
(compressor
loads
up)
until
set
temperature
is
achieved.
An
interval
of
13.5
minutes
is
required
to
maximum
loading
position.
Refer
to
unit
label
diagram
for
unloader
sequencing.
Also
see
Fig.
19.
4.
Step
controller,
7-day
timer
and
proportional
thermo¬
stat
are
factory
set
and
adjusted.
If
other
settings
or
changes
in
adjustment
are
required,
refer
to
dis¬
cussion
of
these
items.
SEVEN-DAY
TIMER
ADJUSTMENT
Factory
settings
are
ON
6:30
A.M.;
OFF
7:30
P.M.
for
each
of
7
days.
1.
On
the
timer
dial
face
(Fig.
18),
loosen
the
thumb¬
screws
which
position
the
system
ON
and
OFF
trippers.
2.
Set
trippers
at
desired
system
ON
and
OFF
time
settings
and
tighten
thumbscrews.
Skipping
a
day(s)
is
accomplished
by
removing
trippers
from
the
dial.
3.
Set
the
timer
by
turning
the
dial
face
clockwise
until
fixed
pointer
indicates
correct
day
and
time.
Do
not
turn
dial
face
counterclockwise.
Do
not
move
fixed
pointer.
PROPORTIONAL
THERMOSTAT
The
propor¬
tional
thermostat,
Fig.
18,
monitors
temperature
of
the
conditioned
air
leaving
unit.
On
signal
from
the
thermo¬
stat,
sequence
motor
operates
cam
switches
to
load
or
unload
compressor
to
maintain
thermostat
setting.
Thermostat
is
factory
set
at
50
F
±
6
F
but
may
be
reset
between
0°F
and
100F
as
follows:
Temperature
Setting
Turn
knob
on
front
of
case
until
pointer
indicates
desired
set
point
temperature.
This
is
the
center
point
of
proportional
range.
Range
Adjustment
Remove
cover
and
turn
adjustment
wheel
until
pointer
indicates
desired
range.
If
sequencer
motor
shaft
constantly
moves
back
and
forth,
increase
proportional
thermostat
range
(about
5
F
at
a
time)
until
system
is
stable.
TERMINAL
POWER
PROPORTIONAL
BLOCK
NO
I
SWITCH
THERMOSTAT
Fig.
18
Control
Panel,
Variable
Volume
Limits