102
APPENDIX D: SystemVut Controller CCN Tables
Maintenance Tables (cont)
TABLE DISPLAY NAME VALUES UNITS POINT NAME WRITE STATUS
OKFCDIAG (cont)
Econ Damper Operational Yes/No DAMPGOOD
OKtoUseFreeCooling? Ye s/No OKFREECL
Ok to Unocc Free Cool? Yes/No OKTOUFC
HEATDIAG
System Demand see Appendix B SYS_DMDT
O p e r a t i n g S u b --- M o d e see Appendix B SUBMTEXT
IGC Fan On Request (IFO) On/Off IGC_IFO
IDF Commanded RPM 0 to 3000 RPM FSPD_RPM
OK to Run Heat Yes/No OKTOHEAT
All Heat Stages Lockout Yes/No ALLHTL OC Forcible
Max Allowed Heat Stages 0to2 MAXHSTGS Forcible
Supply Air Temp Trend xxx.x SATTREND
Supply Air Temperature xxx..x °F SAT
Requested Heating Stages 0to2 REQHSTGS
Heat Stage 1 Timeguard xxx sec TIMGD_H1
Heat Stage 2 Timeguard xxx sec TIMGD_H2
Heat Stage 1 Available Yes/No HT1_AVAL
Heat Stage 2 Available Yes/No HT2_AVAL
Heat Stage 1 Relay On/Off HEAT_1
Heat Stage 2 Relay On/Off HEAT_2
Actual Heat Stage Active x ACT HSTGS
Outdoor Air Temperature xxx.x °F OAT Forcible
Return Air Te mpe rature xxx.x °F RAT Forcible
Fan Supply Air Temp xxx.x °F FST
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
PE_DIAG
0=None
1=MBBRLY11
2=MBBRLY06
PE1 Relay Channel 0to2 PE1_CHAN
PE2 Relay Channel 0to2 PE2_CHAN
PE Turn Off Dead band 0 to 100 % PE_OFFDB
Power Exhaust 1 Relay On/Off PE1 Forcible
Power Exhaust 2 Relay On/Off PE2 Forcible
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
IDF Commanded RPM 0 to 3000 RPM FSPD_RPM
IDF Maximum Fan Speed 0 to 100 % SPEEDMAX
P.Exhaust 1 Curve Offset 0 to 100 % PE1_OFFS
P.Exhaust 2 Curve Offset 0 to 100 % PE2_OFFS
P o w e r E x h a u s t 1 --- S p e e d 1 0 to 100 % PE1_SPD1
P o w e r E x h a u s t 1 --- S p e e d 2 0 to 100 % PE1_SPD2
P o w e r E x h a u s t 1 --- S p e e d 3 0 to 100 % PE1_SPD3
PE Stage 1 At Max Speed 0 to 100 % PE1_PMAX
Power Exhaust 1 --- Pos 1 0 to 100 % PE1_POS1
Power Exhaust 1 --- Pos 2 0 to 100 % PE1_POS2
Power Exhaust 1 --- Pos 3 0 to 100 % PE1_POS3
P o w e r E x h a u s t 2 --- S p e e d 1 0 to 100 % PE2_SPD1
P o w e r E x h a u s t 2 --- S p e e d 2 0 to 100 % PE2_SPD2
P o w e r E x h a u s t 2 --- S p e e d 3 0 to 100 % PE2_SPD3
PE Stage 2 At Max Speed 0 to 100 % PE2_PMAX
Power Exhaust 2 --- Pos 1 0 to 100 % PE2_POS1
Power Exhaust 2 --- Pos 2 0 to 100 % PE2_POS2
Power Exhaust 2 --- Pos 3 0 to 100 % PE2_POS3
VENTDIAG
O p e r a t i n g S u b --- M o d e see Appendix B SUBMTEXT
Ventilation Status see Appendix B VENTTEXT
Ventilation Status see Appendix B VENTST AT
Currently Occupied Yes/No OCCUPIED Forcible