APPENDIX D: SystemVut Controller CCN Tables
Maintenance Tables (cont)
TABLE DISPLAY NAME VALUES UNITS POINT NAME WRITE STATUS
VENTDIAG (cont)
Mins until next occupied --- 1 to 10080 min MINTILOC
FanOnWhenOccupied Yes/No FANON_OC
IDF Commanded RPM 0 to 3000 RPM FSPD_RPM
Free Co oling active Ye s/No FREECOOL
MinPositioninEffect 0 to 100 % MIN_POS Forcible
Requested Damper Pos 0 to 100 % REQDAMP
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
Damper Actual Position 0 to 100 % DAMPPOS
Analog Input IAQ Control 0=NO IAQ,
1=DCV,
2=IAQ OVRD,
3=CTRL MINP
IAQANCFG
Indoor Air Quality Level xxxx PPM IAQ Forcible
OA Quality Level xxxx PPM OAQ Forcible
Differential Air Quality --- 5000 to 5000 PPM AQ_DIFF
AQ Differential High 0 to 5000 DAQ_HIGH
AQ Differential Low 0 to 5000 DAQ_LOW
AQ Diff High IAQOVERRIDE 0 to 5000 PPM AQD_HIGH
AQ Diff Low --- IAQ OVERRIDE 0 to 5000 PPM AQD_LOW
IAQ override enable Yes/No IAQOVREN
IAQ Preoccupancy Purge Yes/No IAQPURGE
Preocc Purge Lockout OAT 0to70 °F IAQP_LA
Ok to Preoccupancy Purge Yes/No OKPREOCC
Preocc Purge Duration 5 t o 120 min IAQPTIME
In Pre--- Occupancy Purge? Ye s/No PREOCCON
Is IAQ Override Active? Yes/No IAQ_OVRD
IAQ Override Switch On/Off IAQ_OVRS Forcible
2--- Pos Damper/ERV Channel 0=NONE,
1=MBB RLY11,
2=MBB RLY06
EV2PCHAN
Supply Air Temperature xxx..x °F SAT
Return Air Te mpe rature xxx.x °F RAT Forcible
Outdoor Air Temperature xxx.x °F OAT Forcible
Damper SAT deadband 0to20 °F T24SATDB
T24 Min Diff in RAT--- OAT 5to20 °F T24RATDF
T24 Heat/Cool End Delay 0to60 min T24CHDLY
SAT heat mode sensing Enable/Disable SAT_HEAT
Actual Heat Stage Active x ACT HSTGS
Actual Cool Stage Active x ACTCSTGS
OKtoUseFreeCooling? Ye s/No OKFREECL
T24 Test Minimum Pos 0 to 100 % T24TSTMN
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
T24 Test Maximum Pos 0 to 100 % T24TSTMX
T24Econ Min Move for SAT 10 to 20 % T24EC STS
Damper Actual Position 0 to 100 % DAMPPOS
VENTCURV
Econ Min at Max Fanspeed 0 t o 100 % MINP_MAX
IDF Maximum Fan Speed 0 to 100 % SPEEDMAX
M i n P o s --- U s e r P o s 1 0 to 100 % MP_UPOS1
M i n P o s --- U s e r P o s 2 0 to 100 % MP_UPOS2
M i n P o s --- U s e r P o s 3 0 to 100 % MP_UPOS3
Min Pos --- User Speed 1 0 to 100 % MP_USPD1
Min Pos --- User Speed 2 0 to 100 % MP_USPD2
Min Pos --- User Speed 3 0 to 100 % MP_USPD3
User Min Pos Pnt 1 Valid Yes/No MP_UPT1
User Min Pos Pnt 2 Valid Yes/No MP_UPT2
User Min Pos Pnt 3 Valid Yes/No MP_UPT3