APPENDIX D: SystemVut Controller CCN Tables
Service Config Tables (cont)
TABLE DISPLAY NAME VALUES UNITS POINT NAME WRITE STA TUS
ECON_CFG (cont)
When to Unocc Free Cool? 0to2 UFC_CFG 1=PreOcc
0=Disabled
1 = P r e --- O c c u p a n c y
2 = Unoccupied
UFC PreOcc Time 1 to 999 min UFCTIME 120
Unocc Free Cool Low Temp --- 30 to 70 °F OATLUFC 50
PE Stage 1 At Max Speed 0 to 100 % PE1_PMAX 40
PE1 Relay Channel 0=NONE,
1=MBB RLY11,
2=MBB RLY06
PE1_CHAN 0: No FIOP
2: FIOP
PE Turn Off Dead band 0 to 100 % PE_OFFDB 5
PE2 Relay Channel 0=NONE,
1=MBB RLY11,
2=MBB RLY06
PE2_CHAN 0 = NONE
PE Stage 2 At Max Speed 0 to 100 % PE2_PMAX 75
T24 Heat/Cool End Delay 0to60 min T24CHDLY 25
T24Econ Min Move for SAT 10 to 20 % T24ECSTS 10
Damper SAT deadband 0to20 °F T24SATDB 12
T24 Min Diff in RAT--- OAT 5to20 °F T24RATDF 15
T24 Test Minimum Pos 0 to 100 % T24TSTMN 15
T24 Test Maximum Pos 0 to 100 % T24TSTMX 85
IAQ_CFG
Analog Input IAQ Control 0to3 IAQANCFG 0: No FIOP
1: CO2 FIOP
0=NoIAQ
1=DCV
2 = IAQ Override
3=MINPOSControl
IAQ Position at Max Fan 0 to 100 % IAQMINP 10
AQ Differential Low 0 to 5000 DAQ_LOW 100
AQ Differential High 0 t o 5000 DAQ_HIGH 700
IAQ Preoccupancy Purge Yes/No IAQPURGE Yes
IAQ Purge Pos at Max IDF 0 to 100 % IAQPMAX 40
Preocc Purge Lockout OAT 0to70 °F IAQP_ LA 50
Preocc Purge Duration 5 to 120 min IAQPTIME 15
IAQ Sensor Value at 4mA 0 to 5000 PPM IAQ_ 4MA 0
IAQ Sensor Value at 20mA 0 to 5000 PPM IAQ_20MA 2000
OAQ Sensor Value at 4mA 0 to 5000 PPM OAQ_4MA 0
OAQ Sensor Value at 20mA 0 to 5000 PPM OAQ_20MA 2000
IAQ override sw channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB Y3
IAQOCHAN 0 = NONE
IAQ Override Switch Type 0=NORM OPEN,
1=NORM CLSD
IAQOSCFG 0=NORMOPEN
ALM_CFG
ALM Relay Assigned Chan 0to2 ALM_CHAN 1=MBBRLY11
0=None
1=MBBRLY11
2=MBBRLY06
Thermostat Alerts Yes/No TSTAT_AL Yes
Hardware Failures Alerts Yes/No HW_AL Yes
SAT/RAT Sensor Alerts Yes/No SATRATAL Ye s
OAT Thermistor Alerts Yes/No OATRL_AL Yes
Space Sensors Alerts Yes/No SPACE_AL Yes
Transducer Sensor Alerts Ye s/No TRANS_AL Yes
RH sensor failure Alert Ye s/No RHS_AL Ye s
Air Quality CO2 Alerts Yes/No CO2S_AL Yes
OACFM Alarm Relay Yes/No OACFM_AL No
Economizer Alerts Yes/No ECON_AL Yes
Dirty Filter Alerts Ye s/No FILT_AL Yes